Section 7—Trip Units
Available Trip Units
PowerPact™ H-, J-, and L-Frame circuit breakers offer a range of thermal-magnetic and
Micrologic™ electronic trip units in interchangeable cases. Thermal-magnetic trip units are
designed to open automatically under overload or short circuit. H-frame and J-frame thermal-
magnetic circuit breakers contain individual thermal (overload) and instantaneous (short circuit)
sensing elements in each pole.
Micrologic electronic trip units provide intelligent operation, with wide setting ranges make
installation upgrades easier. Designed with processing capabilities, Micrologic trip units can
provide measurement information and device operating assistance to supply all of the information
required to manage the electrical installation and optimize energy use.
Micrologic trip units offer excellent measurement accuracy, using a new generation of current
transformers combining “iron-core” sensors for self-powered electronics and “air-core” sensors
(Rogowski coils) for measurements. The protection functions are managed by an ASIC component
that is independent of the measurement functions. This independence ensures immunity to
conducted and radiated disturbances and a high level of reliability.
An LED on the front of the electronic trip units indicates the result of the self-test running continuously on
the measurement system and the tripping release. When the green LED is flashing, the links between
the CTs, the processing electronics and the Mitop release are operational. The circuit breaker is ready
to protect. A minimum current of 15 to 50 A, depending on the device, is required for this function.
The dual adjustment for protection functions on Micrologic 5/6 consists of:
an adjustment using rotary switches sets the maximum value
an adjustment, made using the keypad or remotely, fine-tunes the setting. This setting may not
exceed the first one. It can be read directly on the Micrologic screen, to within one ampere and
a fraction of a second.
NOTE: All the trip units have a transparent sealable cover that protects access to the adjustment
rotary switches.