Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
Energy Management
80
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Communication Components and FDM128 Connections
The FDM128 degree of protection is IP65 at the touch screen cover. IP54 is maintained after
installation by using the supplied gasket.
Figure 6: FDM128 Connections
DB416931.eps
A. FDM128
B. IFE Modbus Interface
C. NSX Cord
D. Internal Terminal Block for Communication via NSX Cord
E. BSCM Module
F. Prefabricated wiring
G. Micrologic Trip Unit
H. FDM121 Display
I. RJ45 Cable
J. Line Terminator (on unused connector if applicable)
K. I/O Module
Connections
PowerPact circuit breaker is connected to the I/O module or FDM121
display unit via the internal terminal block for the NSX cord equipped
with an RJ45 connector:
Cord is available in three lengths: 0.98 ft. (0.35 m), 4.3 ft. (1.3 m)
and 9.8 ft. (3 m).
Lengths up to 32.9 ft. (10 m) are possible using extensions.
The FDM121 display unit and the I/O module are connected to:
the IFM Modbus interface by a communication cable with RJ45
connectors on both ends
or
the IFE Ethernet interface module by a communication cable with
RJ45 connectors on both ends.
0.98 ft.
(0.35 m)
4.3 ft.
(1.3 m)
9.8 ft.
(3 m)
I
J
G
B
C
D
F
E
J
K
H
Communication Components and Connections
24 Vdc
Ethernet
Ethernet
ULP
24 Vdc
A