Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Energy Management
75
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Screens
Main Menu
When powered up, the FDM121 screen automatically displays the ON/OFF status of the device.
When not in use, the screen is not backlit. Backlighting can be activated by pressing one of the
buttons. It goes off after three minutes.
Fast Access to Essential Information
•
“Quick view” provides access to five screens that display a summary of essential operating
information (I, U-V, f, P, E, THD, circuit breaker ON/OFF).
Access to Detailed Information
•
“Metering” can be used to display the measurement data (I, U-V, f, P, Q, S, E, THD, PF) with the
corresponding min/max values.
•
“Alarms” displays active alarms and the alarm history.
•
“Services” provides access to the operation counters, energy and maximum ammeter reset
function, maintenance indicators, identification of modules connected to the internal bus, and
FDM121 internal settings (language, contrast, etc.).
Communication Components and FDM121 Connections
The FDM121 degree of protection is IP54 in front. IP54 is maintained after switchboard mounting by
using the supplied gasket during installation.
Quick View
Metering
Control
Alarms
Services