Additional Technical Characteristics
Measurement accuracy of the entire measurement system, including the sensors:
Current: +/- 1%
Voltage: +/- 0.5%
Power and energy: +/- 2%
Frequency: +/- 0.1%
Operating-Assistance Functions Characteristics
Micrologic Trip Unit Alarms with Time-Stamping
Alarm Types
The user can assign an alarm to all Micrologic A or E trip unit measurements or events:
up to 12 alarms can be used together:
two alarms are predefined and activated automatically:
Micrologic 5 trip unit: overload (I
r
)
Micrologic 6 trip unit: overload (I
r
) and ground fault (I
g
)
thresholds, priorities and time delays can be set for ten other alarms.
the same measurement can be used for different alarms to precisely monitor certain values, e.g.
the frequency or the voltage
alarms can also be assigned to various states: phase lead/lag, four quadrants, phase sequence
selection of display priorities, with screen displaying a window showing high priority alarm
alarm time-stamping.
Alarm Settings
Alarms cannot be set using the keypad or the front display module. They are set through the
communication network with the PC. Set-up includes the threshold, priority, activation delay before
display and deactivation delay. It is also possible to reprogram the standard assignment for the two
SDx relay outputs to user-selected alarms.
Alarm Reading
Remote alarm indicators:
reading on the front display module or on a PC through the communication network
system remote indicators using SDx relay with two output contacts for alarms
Micrologic trip unit built-in LCD display
Histories and Event Tables
Micrologic A and E trip unit have histories and event tables that are always active.
Three types of time-stamped histories
Tripping due to overruns of I
r
, I
sd
, I
i
, I
g
: last 17 trips
Alarms: last 10 alarms
Operating events: last 10 events
Each history record is stored with:
indicators in clear text in a number of user-selectable languages
time-stamping: date and time of event
status: pick-up / drop-out