Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
Motor Circuit Protection
60
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Table 57: H-Frame (150 A), J-Frame (250 A) and L-Frame (600 A) Electronic Motor Protector Circuit Breakers
(UL Ratings)—Two Device Solutions
1
Electronic
Trip Unit
Type
Frame
Sensor
Rating
Trip
Unit
Full Load
Amperes
Range (FLA)
I
sd
(x FLA)
G Interrupting
Cat. No.
J Interrupting
Cat. No.
L Interrupting
Cat. No.
R Interrupting
Cat. No.
Standard
2
H-Frame
30
2.2 M
14–25 5-13 x FLA HGL36030M38X HJL36030M38X HLL36030M38X HRL36030M38X
50 14–42 5-13 x FLA HGL36050M38X HJL36050M38X HLL36050M38X HRL36050M38X
100 30–80 5-13 x FLA HGL36100M38X HJL36100M38X HLL36100M38X HRL36100M38X
150 58–130 5-13 x FLA HGL36150M38X HJL36150M38X HLL36150M38X HRL36150M38X
J-Frame 250 114–217 5-13 x FLA JGL36250M38X JJL36250M38X JLL36250M38X JRL36250M38X
L-Frame
400
2.3 M
190–348 5-13 x FLA LGL36400M38X LJL36400M38X LLL36400M38X LRL36400M38X
600 312–520 5-13 x FLA LGL36600M38X LJL36600M38X LLL36600M38X LRL36600M38X
1
Two-device solutions (these electronic motor protector circuit breakers include short circuit and overload protection)
—1 electronic motor circuit protector with a Micrologic 2.2 M electronic trip unit, plus
—1 contactor
2
The standard trip unit offers Class 5, 10 and 20 and phase unbalance or phase loss protection.