Trip Class
The class is selected as a function of the normal motor starting time.
Class 5: starting time less than 5 s
Class 10: starting time less than 10 s
Class 20: starting time less than 20 s
For a given class, it is necessary to check that all motor-feeder components are sized to carry the
6 x FLA starting current without excessive temperature rise during the time corresponding to the
class.
Short-Circuits
Short-time protection (I
sd
)
Provides protection with an adjustable pick-up I
sd
.
There is a very short delay to let through motor starting currents.
Non-adjustable instantaneous protection (l
i
)
Instantaneous protection with non-adjustable pick-up l
i
.
Phase Unbalance or Phase Loss (l
unbal
)
This function opens the circuit breaker if a phase unbalance occurs:
that is greater than the 30% fixed pick-up I
unbal
following the non-adjustable time delay t
unbal
equal to:
• 0.7 s during starting
• 4 s during normal operation
Phase loss is an extreme case of phase unbalance and leads to tripping under the same
conditions.
Indications
Front indications
The green “Ready” LED blinks slowly when the electronic trip unit is ready to provide protection. It
indicates the trip unit is operating correctly.
Red alarm LED for motor operation goes ON when the thermal image of the rotor and stator is
greater than 95% of the permissible temperature rise.
Remote indications using SDTAM module
PowerPact H-, J-, and L-frame devices with a Micrologic 2 M trip unit can be equipped with an
SDTAM module dedicated to motor applications for:
A contact to indicate circuit-breaker overload.
A contact to open the contactor. In the event of a phase unbalance or overload, this output is
activated 400 ms before circuit-breaker tripping to open the contactor and avoid circuit breaker
tripping
This module takes the place of the shunt trip (MN)/undervoltage trip (MX) coils and an auxiliary
switch (OF) contact
SDTAM remote indication relay module with its terminal block.
Note: All the trip units have a transparent sealable cover that protects access to the adjustment rotary
switches.