Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
Automatic Switches
48
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Table 46: PowerPact L-Frame 600 A Unit-Mount Automatic Molded Case Switches, 600 Vac
Ampere
Rating
Poles
1
1
Four-pole circuit breaker available as bus connected, with lug configurations, and in plug-in, draw-out and rear-connected
configurations.
Cat. No. Withstand Rating
2
2
The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when
protected by a circuit breaker or fuse with an equal continuous current rating.
Trip
Point
Standard Lug Terminal
Wire Range
240 Vac 480 Vac 600 Vac
Unit-Mount Automatic Molded Case Switches
G Withstand
400 A
3
LGL36000S40X 65 kA 35 kA 18 kA 4800 A
AL600LS52K3
(2) 2 AWG–500 kcmil Al/Cu
600 A LGL36000S60X 65 kA 35 kA 18 kA 6600 A
400 A
4
LGL46000S40X 65 kA 35 kA 18 kA 4800 A
AL600LS52K4
(2) 2 AWG–500 kcmil Al/Cu
600 A LGL46000S60X 65 kA 35 kA 18 kA 6600 A
L Withstand
400 A
3
LLL36000S40X 125 kA 100 kA 50 kA 4800 A
AL600LS52K3
(2) 2 AWG–500 kcmil Al/Cu
600 A LLL36000S60X 125 kA 100 kA 50 kA 6600 A
400 A
4
LLL46000S40X 125 kA 100 kA 50 kA 4800 A
AL600LS52K4
(2) 2 AWG–500 kcmil Al/Cu
600 A LLL46000S60X 125 kA 100 kA 50 kA 6600 A
R Withstand
400 A
3
LRL36000S40X 200 kA 200 kA 100 kA 4800 A
AL600LS52K3
(2) 2 AWG–500 kcmil Al/Cu
600 A LRL36000S60X 200 kA 200 kA 100 kA 6600 A
400 A
4
LRL46000S40X 200 kA 200 kA 100 kA 4800 A
AL600LS52K4
(2) 2 AWG–500 kcmil Al/Cu
600 A LRL46000S60X 200 kA 200 kA 100 kA 6600 A
I-Line Circuit Breakers Automatic Molded Case Switches
G Withstand
400 A
3
LGA36000S40X 65 kA 35 kA 18 kA 4800 A
AL600LF52K3
(2) 3/0 AWG–500 kcmil Al/Cu
600 A LGA36000S60X 65 kA 35 kA 18 kA 6600 A
L Withstand
400 A
3
LLA36000S40X 125 kA 100 kA 50 kA 4800 A
AL600LF52K3
(2) 3/0 AWG–500 kcmil Al/Cu
600 A LLA36000S60X 125 kA 100 kA 50 kA 6600 A
R Withstand
400 A
3
LRA36000S40X 200 kA 200 kA 100 kA 4800 A
AL600LF52K3
(2) 3/0 AWG–500 kcmil Al/Cu
600 A LRA36000S60X 200 kA 200 kA 100 kA 6600 A
Table 47: L-Frame Ratings and Withstand Ratings
Circuit Breaker 400 A 600 A
Number of Poles 3, 4 3, 4
Ampere Rating (A) 400 600
UL 489 Ratings
Rated Voltage (V) 600 600
IEC 60947-3 ratings
Rated Insulation Voltage (V) 750 750
Rated Impulse Withstand Voltage (kV) 8 8
Rated Operational Voltage Ue AC 50/60 Hz 690 690
Rated Operational Current Ie AC 525 V 400 600
Making Capacity (kA peak) 7.1 8.5
Short-Time Withstand Current (kA rms) Icw
Icw (kA ms) 5 6