Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Automatic Switches
47
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Catalog Numbers
Table 44: PowerPact H-Frame and J-Frame 250 A Unit-Mount Automatic Molded Case
Switches, 600 Vac with Factory Sealed Trip Unit (Suitable for Reverse Connection)
Ampere
Rating
2-pole 3-pole Withstand Rating
1
1
The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when
protected by a circuit breaker or fuse with an equal continuous current rating.
Trip
Point
Standard Lug Kit
Terminal Wire Range
Cat. No. Cat. No. 240 Vac 480 Vac 600 Vac
G Withstand
150 A HGL26000S15
2
2
Two-pole device with 3 in. (76 mm) mounting height, all other two-pole circuit breakers use three-pole switch 4.5 in. (114 mm)
mounting height.
HGL36000S15 65 35 18 2250 A
AL150HD
#14–#3/0 AWG Al or Cu
175 A JGL26000S17 JGL36000S17 65 35 18 3125 A
AL175JD
#4–#4/0 AWG Al or Cu
250 A JGL26000S25 JGL36000S25 65 35 18 3125 A
AL250JD
#3/0–350 kcmil Al or Cu
L Withstand
150 A HLL26000S15 HLL36000S15 125 100 50 2250 A
AL150HD
#14–#3/0 AWG Al or Cu
175 A JLL26000S17 JLL36000S17 125 100 50 3125 A
AL175JD
#4–#4/0 AWG Al or Cu
250 A JLL26000S25 JLL36000S25 125 100 50 3125 A
AL250JD
#3/0–350 kcmil Al or Cu
R Withstand
175 A — JRL36000S17 200 200 100 3125 A
AL175JD
#4–#4/0 AWG Al or Cu
250 A — JRL36000S25 200 200 100 3125 A
AL250JD
#3/0–350 kcmil Al or Cu
Table 45: PowerPact H-Frame and J-Frame I-Line Automatic Molded Case Switches, 600 Vac
with Factory Sealed Trip Unit (Suitable for Reverse Connection)
Ampere
Rating
2-pole 3-pole Withstand Rating
1
1
The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when
protected by a circuit breaker or fuse with an equal continuous current rating.
Trip
Point
Standard Lug Kit
Terminal Wire Range
Cat. No. Cat. No. 240 Vac 480 Vac 600 Vac
G Withstand
150 A HGA26000S15( )
2
2
Two-pole device with 3 in. (76 mm) mounting height, all other two-pole circuit breakers use three-pole 4.5 in. (114 mm) mounting
height.
HGA36000S15 65 35 18 2250A
AL150HD
#14–#3/0 AWG Al or Cu
175 A JGA26000S17( ) JGA36000S17 65 35 18 3125 A
AL175JD
#4–#4/0 AWG Al or Cu
250 A JGA26000S25( ) JGA36000S25 65 35 18 3125 A
AL250JD
#3/0–350 kcmil Al or Cu
L Withstand
150 A HLA26000S15( ) HLA36000S15 125 100 50 2250 A
AL150HD
#14–#3/0 AWG Al or Cu
175 A JLA26000S17( ) JLA36000S17 125 100 50 3125 A
AL175JD
#4–#4/0 AWG Al or Cu
250 A JLA26000S25( ) JLA36000S25 125 100 50 3125 A
AL250JD
#3/0–350 kcmil Al or Cu
R Withstand
175 A JRA26000S17( ) JRA36000S17 200 200 100 3125A
AL175JD
#4–#4/0 AWG Al or Cu
250 A JRA26000S25( ) JRA36000S25 200 200 100 3125A
AL250JD
#3/0–350 kcmil Al or Cu