Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Automatic Switches
46
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Specifications
Table 42: H-Frame Automatic Molded Case Switch Specifications
Frame H-Frame
Withstand Rating “G” “L”
UL 489
Poles Two-Pole Three-Pole Two-Pole
1
Three-Pole
Catalog Number
150 A HGL26000S15 HGL3600S15 HLL26000S15 HLL36000S15
175 A — — — —
250 A — — — —
Withstand Ratings
240 Vac 65 kA 65 kA 125 kA 125 kA
480 Vac 35 kA 35 kA 100 kA 100 kA
600 Vac 18 kA 18 kA 50 kA 50 kA
250 Vdc 20 kA 20 kA 20 kA 20 kA
AC Trip Point 2250 A 2250 A 2250 A 2250 A
IEC 60947-3
Rated Insulation Voltage 750 Vac 750 Vac 750 Vac 750 Vac
Rated Impulse Withstand Voltage 8 kV 8 kV 8 kV 8 kV
Rated Operational Voltage
ac 525 Vac 525 Vac 525 Vac 690 Vac
dc — — — —
1
Two-pole devices use a three-pole switch frame with the center pole inoperative.
Table 43: J-Frame Automatic Molded Case Switch Specifications
Frame J-Frame
Withstand Rating “G” “L” “R”
UL 489
Poles Two-Pole
1
1
Two-pole devices use a three-pole switch frame with the center pole inoperative.
Three-Pole Two-Pole
1
Three-Pole Three-Pole
Catalog Number
150 A — — — — —
175 A JGL26000S17 JGL36000S17 JLL26000S17 JLL36000S17 JRL36000S17
250 A JGL26000S25 JGL36000S25 JLL26000S25 JLL36000S25 JRL36000S25
Withstand Ratings
240 Vac 65 kA 65 kA 125 kA 125 kA 200 kA
480 Vac 35 kA 35 kA 100 kA 100 kA 200 kA
600 Vac 18 kA 18 kA 50 kA 50 kA 100 kA
250 Vdc 20 kA 20 kA 20 kA 20 kA 20 kA
AC Trip Point 3125 A 3125 A 3125 A 3125 A 3125 A
IEC 60947-3
Rated Insulation Voltage 750 Vac 750 Vac 750 Vac 750 Vac 750 Vac
Rated Impulse Withstand Voltage 8 kV 8 kV 8 kV 8 kV 8 kV
Rated Operational Voltage
ac 525 Vac 525 Vac 525 Vac 525 Vac 690 Vac
dc 500 Vdc 500 Vdc 500 Vdc 500 Vdc 500 Vdc