Circuit Breakers with Field-Interchangeable Trip Units Catalog Numbers
Table 26: H-Frame 150 A Circuit Breaker Frame
1
with Field-Interchangeable
Thermal-Magnetic Trip Units
2
(Three-Pole, 600 Vac, 250 Vdc)
1
Standard lug kit: AL150HD. Terminal wire range: 14–3/0 AWG Al or Cu.
2
Circuit breakers will be labeled with Line and Load markings and are not suitable for reverse connections.
Available on three-pole circuit breakers. Not allowed in I-Line, plug-in, or drawout devices. Not available in R interrupting rating.
Ampere
Rating
Fixed AC
Magnetic Trip
Interrupting Rating
DGJ
3
3
UL Listed/CSA Certified as current-limiting circuit breakers.
L
3
Hold Trip Cat. No. Cat. No. Cat. No. Cat. No.
15 A 350 A 750 A HDL36015T
4
4
For 100% rated circuit breakers replace the “T” suffix with “R.” Not available in I-Line, plug-in, or drawout constructions. Not
available in R interrupting rating.
HGL36015T HJL36015T HLL36015T
20 A 350 A 750 A HDL36020T HGL36020T HJL36020T HLL36020T
25 A 350 A 750 A HDL36025T HGL36025T HJL36025T HLL36025T
30 A 350 A 750 A HDL36030T HGL36030T HJL36030T HLL36030T
35 A 400 A 850 A HDL36035T HGL36035T HJL36035T HLL36035T
40 A 400 A 850 A HDL36040T HGL36040T HJL36040T HLL36040T
45 A 400 A 850 A HDL36045T HGL36045T HJL36045T HLL36045T
50 A 400 A 850 A HDL36050T HGL36050T HJL36050T HLL36050T
60 A 800 A 1450 A HDL36060T HGL36060T HJL36060T HLL36060T
70 A 800 A 1450 A HDL36070T HGL36070T HJL36070T HLL36070T
80 A 800 A 1450 A HDL36080T HGL36080T HJL36080T HLL36080T
90 A 800 A 1450 A HDL36090T HGL36090T HJL36090T HLL36090T
100 A 900 A 1700 A HDL36100T HGL36100T HJL36100T HLL36100T
110 A 900 A 1700 A HDL36110T HGL36110T HJL36110T HLL36110T
125 A 900 A 1700 A HDL36125T HGL36125T HJL36125T HLL36125T
150 A 900 A 1700 A HDL36150T HGL36150T HJL36150T HLL36150T
Table 27: J-Frame 250 A Circuit Breaker Frame with Field-Interchangeable
Thermal-Magnetic Trip Units
1
(Three-Pole, 600 Vac, 250 Vdc)
1
Circuit breakers will be labeled with Line and Load markings and are not suitable for reverse connections.
Available on three-pole circuit breakers. Not allowed in I-Line, plug-in, or drawout devices. Not available in R interrupting rating.
Ampere
Rating
Adjustable AC
Magnetic Trip
Interrupting Rating
DG J
2
2
UL Listed/CSA Certified as current-limiting circuit breakers.
L
3
Low High Cat. No. Cat. No. Cat. No. Cat. No.
150 A
3
3
Standard lug kit: AL175JD. Terminal wire range: 4–4/0 AWG Al or Cu.
750 A 1500 A JDL36150T
4
4
For 100% rated circuit breakers replace the “T” suffix with “R.” Not available in I-Line, plug-in, or drawout constructions. Not
available in R interrupting rating.
JGL36150T JJL36150T JLL36150T
175 A
3
875 A 1750 A JDL36175T JGL36175T JJL36175T JLL36175T
200 A
5
5
Standard lug kit: AL250JD. Terminal wire range: 3/0 AWG–350 kcmil Al or Cu.
1000 A 2000 A JDL36200T JGL36200T JJL36200T JLL36200T
225 A
5
1125 A 2250 A JDL36225T JGL36225T JJL36225T JLL36225T
250 A
5
1250 A 2500 A JDL36250T JGL36250T JJL36250T JLL36250T