Table 19: PowerPact J-Frame 250 A Unit-Mount Thermal-Magnetic Circuit Breakers with Factory Sealed Trip Unit
(Suitable for Reverse Connection)
Current
Rating
at 104°F
(40°C)
Adjustable AC
Magnetic Trip
Interrupting Rating
DGJ
1
L
1
R
1
Hold Trip
Standard
(80%)
Rated
100%
Rated
Standard
(80%)
Rated
100%
Rated
Standard
(80%)
Rated
100%
Rated
Standard
(80%)
Rated
100%
Rated
Standard
(80%)
Rated
100%
Rated
J-Frame, 250 A, Two-Pole, 600 Vac 50/60 Hz, 250 Vdc
150 A
2
750 A 1500 A JDL26150 JDL26150C JGL26150 JGL26150C JJL26150 JJL26150C JLL26150 JLL26150C ——
175 A
2
875 A 1750 A JDL26175 JDL26175C JGL26175 JGL26175C JJL26175 JJL26175C JLL26175 JLL26175C ——
200 A
3
1000 A 2000 A JDL26200 JDL26200C JGL26200 JGL26200C JJL26200 JJL26200C JLL26200 JLL26200C ——
225 A
3
1125 A 2250 A JDL26225 JDL26225C JGL26225 JGL26225C JJL26225 JJL26225C JLL26225 JLL26225C ——
250 A
3
1250 A 2500 A JDL26250 JDL26250C JGL26250 JGL26250C JJL26250 JJL26250C JLL26250 JLL26250C ——
J-Frame, 250 A, Three-Pole, 600 Vac 50/60 Hz, 250 Vdc
150 A
2
750 A 1500 A JDL36150 JDL36150C JGL36150 JGL36150C JJL36150 JJL36150C JLL36150 JLL36150C JRL36150 JRL36150C
175 A
2
875 A 1750 A JDL36175 JDL36175C JGL36175 JGL36175C JJL36175 JJL36175C JLL36175 JLL36175C JRL36175 JRL36175C
200 A
3
1000 A 2000 A JDL36200 JDL36200C JGL36200 JGL36200C JJL36200 JJL36200C JLL36200 JLL36200C JRL36200 JRL36200C
225 A
3
1125 A 2250 A JDL36225 JDL36225C JGL36225 JGL36225C JJL36225 JJL36225C JLL36225 JLL36225C JRL36225 JRL36225C
250 A
3
1250 A 2500 A JDL36250 JDL36250C JGL36250 JGL36250C JJL36250 JJL36250C JLL36250 JLL36250C JRL36250 JRL36250C
1
UL Listed/CSA Certified as current-limiting circuit breakers.
2
Standard lug kit: AL175JD. Terminal wire range: 4–4/0 AWG Al or Cu.
3
Standard lug kit: AL250JD. Terminal wire range: 3/0 AWG–350 kcmil Al or Cu.