Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
Trip Curves
245
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Figure 122: Micrologic 1.3 M Electronic Trip Unit Instantaneous Trip Curve
MICROLOGIC™ ELECTRONIC TRIP UNITS
Micrologic™ 1.3M Instantaneous Trip Curve
400A L-Frame
The time-current curve information is to be used
for application and coordination purposes only.
Notes:
1. Total clearing times shown include the
response times of the trip unit, the circuit
breaker opening, and the extinction of the
current.
Curves apply from -35ºC to +70ºC (-31ºF to
+158ºF) ambient temperature.