Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Trip Curves
214
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Figure 92: H- and J-Frame Motor Circuit Protector
!"
!"
!"
!"
#
#
#
#
#
#
$&'$+,::;&<=
,
,
=
,
:
:
;
&
<
=
;
&
:
$
>
+
,
$
>
?
@
,
K#
#
#
#
#
#
#
#
:
K
&=:$&:$&,?'=Q;Z?;&:
POWERPACT H/J FRAME MOTOR CIRCUIT PROTECTOR
WITH MANUAL SETTINGS
CHARACTERISTIC TRIP CURVE NO. 045-1
The time-current curve information represents the typical response and is to
be used for application and coordination purposes only.
Curves apply from -30C to +60C ambient temperature.
Notes:
• The MCP is an instantaneous only breaker that detects the peaks of the
current. In order to trip within the specified time-current levels, consecutive
peaks of the current must exceed the selected setting’s threshold.
• Total clearing times shown include the response times of the trip unit, the
circuit breaker opening, and the extinction of the current.
• The time-current curve represents single-phase to three-phase fault currents.
MOTOR CIRCUIT PROTECTOR INFORMATION
Suffix # FLA Adjustments
M71 1.5 3 6 8 11 14 17 20 25
M72 14 17 21 24 27 29 32 36 42
M73 30 35 41 46 51 56 63 71 80
M74 58 71 79 86 91 97 110 119 130
M75 114 137 145 155 163 172 181 210 217
Suffix Lowest Highest IM
# Setting Setting Adjustment
M71 12 325 8x 9x 10x 11x 12x 13x
M72 112 546 8x 9x 10x 11x 12x 13x
M73 240 1040 8x 9x 10x 11x 12x 13x
M74 464 1690 8x 9x 10x 11x 12x 13x
M75 912 2500 8x 9x 10x 11x 12x 13x
Suffix # Nominal Fault Current Level Maximum Clearing Time
M71 670
M72 1150
M73 2150 1/2-1 Cycle
M74 3450
M75 3600
© 2006 Schneider Electric all rights reserved
Curve No. 0045TC0601
August 2006
Drawing No. 48095-045-01