Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
General Information
18
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Special Ratings
The H-frame and J-frame circuit breakers also comply with the following special ratings:
HACR rating
SWD switch duty rating (applies only to 15 and 20 A / 277 Vac or less, two- and three-pole)
HID high intensity discharge lighting rating (15–50 A)
The L-frame circuit breakers complies with the following special rating:
HACR rating
Marine Ratings
UL Marine Listed/CSA Certified Circuit Breakers (UL 489 Supplement SA)
The PowerPact H- and J-frame circuit breakers with thermal-magnetic trip units with D, G, J and L
interruption levels meet the UL 489 Supplement SA requirements for use on vessels of any length
under or over 65 ft. (19.8 m). The PowerPact H-, J-, and L-frame circuit breakers with Micrologic
electronic trip units meet the UL 489 Supplement SA for use on vessels over 65 ft. (19.8 m) in length.
Marine circuit breakers must not use aluminum or aluminum alloys for terminal connections and must
be calibrated at an ambient temperature of 104°F (40°C). Standard circuit breakers should not be
specified or used in the place of marine rated circuit breakers.
Circuit breakers can be ordered with the Marine SA listing by adding the suffix “YA” (marine) to the
catalog number.
UL Naval Listed/CSA Certified Circuit Breakers (UL 489 Supplement SB)
The PowerPact H-, J-, and L-frame circuit breakers with Micrologic trip units with D, G, J and L
interruption levels meet the UL 489 Supplement SB requirements for use on naval vessels. These circuit
breakers are subject to various vibration tests as described in UL 489 Supplement SB. Naval circuit
breakers must not use aluminum or aluminum alloys for terminal connections and must be calibrated at
an ambient temperature of 122°F (50°C). Standard circuit breakers should not be specified or used in the
place of navel rated circuit breakers.
Circuit breakers can be ordered with the Naval SB listing by adding the suffix “YA1” (naval) to the catalog
number.
American Bureau of Shipping (ABS)
The PowerPact H-, J-, and L-Frame circuit breakers are certified to ABS-NVR (American Bureau of
Shipping - Naval Vessel Rules), for use on Naval vessels.