Brochure

PowerPact H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams
162
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Symbols Communicating Motor Operator
Q:
B4, A1:
BSCM:
Circuit Breaker
Motor Operator Power Supply
Breaker Status and Control Module
RSU Screen for Communicating Motor Operator
Single-line diagram of communicating motor operator
Opening, closing and reset orders are transmitted through the communication
network. The “Enable automatic reset” and “Enable reset even if SDE”
parameters must be set using the RSU software using the screen by clicking the
blue text.
“Auto/Manu” is a switch on the front of the motor operator.
Terminal connections shown as O must be connected by the customer.
Motor Operator
(continued)
+
-
L
H
Q
B4
A1
Vac (220/240 V)
Vac
0I
auto
manu
NSX cord
BSCM
NOTE: Schematic of the communicating motor operator .
Open motor
Open
command
220
VAC
OF OF
SD
Close
command
Reset
command
Enable
automatic
reset
Enable
reset
even if
SDE
SDE
SD
B4
A1
Close motor Reset motor
Auto
Manu
RSU utility setup screen for the
communicating motor operator