Brochure
PowerPact H-, J-, and L-Frame Circuit Breakers
Circuit Breaker Mounting and Connections
147
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Power Distribution Connectors
The power distribution connectors (PDC) can be used for multiple load wire connections on one circuit
breaker. Use in place of standard distribution blocks to save space and time. Field installable kit
includes tin-plated aluminum lug, connectors, and required mounting hardware.
•
For use on load end of circuit breaker only
•
For use in UL 508 Industrial Control applications
•
For use in UL 1995/CSA C22.2 No. 236 heating and cooling equipment
•
For copper wire only
See Table 135 for the phase barriers for power distribution connectors.
Table 132: Power Distribution Connectors
Frame Kit Number
Qty per
Kit
Wires per Terminal Wire Range
Wire Binding
Screw Torque
H-Frame
PDC6HD6 36
8–6 AWG
(10–16 mm
2
)
25 lb-in.
(2.8 N•m)
14–10 AWG
(2.5–6 mm
2
)
20 lb-in.
(2.3 N•m)
PDC3HD2 33
2 AWG
(35 mm
2
)
40 lb-in.
(4.5 N•m)
14–3 AWG
(2.5–35 mm
2
)
35 lb-in.
(4.0 N•m)
J-Frame
PDC6JD4 36
8–4 AWG
(10–25 mm
2
)
35 lb-in.
(4.0 N•m)
14–10 AWG
(2.5–6 mm
2
)
20 lb-in.
(2.3 N•m)
PDC3JD20 3
3 total
2
14–6 AWG Cu
(2.5–16 mm
2
) or
4–1 AWG Cu
(25–50 mm
2
)
35 lb-in.
(4.0 N•m)
40 lb-in.
(4.5 N•m)
and 1
3–2/0 AWG Cu
(35–70 mm
2
)
50 lb-in.
(5.6 N•m)
L-Frame
PDC5DG20L3
1
1
Kit includes terminal shield.
3
5 total
3
4–1 AWG
(25–50 mm
2
) or
14–6 AWG
(2.5–16 mm
2
)
40 lb-in.
(4.5 N•m)
35 lb-in .
(4.0 N•m)
and 2
3–2/0 AWG
(35–70 mm
2
)
50 lb-in.
(5.6 N•m)
PDC12DG4L3
1
312
8–4 AWG
(10–25 mm
2
)
35 lb-in.
(4.0 N•m)
14–10 AWG
(2.5–6 mm
2
)
20 lb-in.
(2.3 N•m)