PowerPact H-, J-, and L-Frame Circuit Breakers
Circuit Breaker Mounting and Connections
142
02/2016 © 2011–2016 Schneider Electric
All Rights Reserved
Drawout Mounting
The cradle is made up of two side plates installed on the plug-in base and two other plates mounted on
the circuit breaker.
The drawout mounting provides all of the functions of the plug-in base, plus:
Disconnected position—the power circuit is disconnected, the circuit breaker is simply withdrawn
and may still be operated (on, off, push-to-trip)
Circuit breaker may be locked using 1 to 3 padlocks, diameter 0.19 to 0.31 inch (5–8 mm), to
prevent connection
Auxiliaries can be tested using manual auxiliary connector
Drawout mounting is on a backplate:
Through a front panel or on rails
Horizontally or vertically
Accessories for drawout circuit breakers:
Auxiliary contacts indicator for installation on the fixed part of the cradle, indicating the “connected”
and “disconnected” position
Toggle collar for circuit breakers with toggle through front panel, intended to maintain the degree of
protections whatever the position of the circuit breakers (supplied with a toggle extension)
Keylock which can be used to
Prevent insertion for connection
Lock the circuit breaker in the connected or disconnected position
Telescopic shaft for extended rotary handles
Control voltage, which is provided through automatic secondary disconnect in the connected
position only. Electrical accessories can be tested in the disconnected position with an external
wiring harness.
The drawout-mounted cradle is listed under UL file E113555 and certified under CSA file LR69561.
Figure 12: Drawout Mounting Positions
Connected Disconnected Removed