Class 9421 NEMA Door Mounted Rotary Operating Handles
Table 101: Rotary Operated Handles
H- and J-Frame
1
L-Frame
Device Description
Factory
Installed
Suffix
Field
Installable
Kit No.
Factory
Installed
Suffix
Field
Installable
Kit No.
Direct
Mounted
Standard Handle Black Handle only RD10 S29337 RD10 S32597
Standard Black Handle with
One early-break switch RD12
S29337 +
S29345
RD12
S32597 +
S32605
Two early-make switches RD13
S29337 +
S29346
RD13
S32597 +
S29346
Red handle on yellow bezel
Handle Only RD20 S29339 RD20 S32599
One early-break switch RD22
S29339 +
S29345
RD22
S32599 +
S32605
Two early-make switches RD23
S29339 +
S29346
RD23
S32599 +
S29346
MCC Conversion Accessory S429341 S32606
CNOMO Conversion Accessory S29342 S32602
Door Mounted
Standard black handle Handle Only RE10 S29338 RE10 S32598
Standard Black Handle with: Two early make switches RE13
S29338 +
S29345
RE13
S32598 +
S32605
Red handle on yellow bezel Handle Only RE20 S29340 RE20 S32600
Telescoping RT10 S29343 RT10 S32603
Accessories
Key lock adapter S429344 S32604
Key locks
Ronis 1351.500 S41940 S41940
Profalux KS5 B24 D4Z S42888 S42888
2 Ronis keylocks with 1 key S41950 S41950
2 Profalux keylocks with 1 key S42878 S42878
Indication Auxiliary Switch
One early-break switch S29345 S32605
Two early-make switches S29346 S29346
1
Not available in H-frame two-pole modules.
Installation
The extended rotary operating handle is made up of:
A mounting plate that provides a rotary actuator for a standard toggle circuit breaker
Handle assemblies available for NEMA 3, 3R, 4, and 4X
Available in standard or short (3 in.) handle assemblies
Operation
The door mounted operating handle makes it possible to operate a circuit breaker installed in an enclosure with
the enclosure door closed.
Provides ON (I) and OFF (O) indication
The circuit breaker may be locked in the off position
Shaft Length
The shaft length is the distance between the back of the circuit breaker and the door:
Minimum mounting depth is 5.5 in. (138 mm)
Maximum mounting depth is 10.75 in. (273 mm) with standard shaft
Maximum mounting depth is 21.3 in. (543 mm) with long shaft
H- and J-Frame Class 9421 Door-Mounted Operating Mechanism
Description Catalog No.
Standard Shaft Kit 9421LJ1
Long Shaft Kit 9421LJ4