PowerPact H-, J-, and L-Frame Circuit Breakers
Accessories and Auxiliaries
127
02/2016
© 2011–2016 Schneider Electric
All Rights Reserved
Rotary Operating Handles
Directly Mounted Rotary Operating Handles
Door-Mounted (Extended) Rotary Operating Handle
Directly Mounted Rotary
Operating Handle
p
u
s
h
to
t
r
ip
Installation
The directly mounted rotary operating handle replaces the circuit breaker front accessory cover (secured by screws).
Operation
The direct rotary handle maintains:
Suitability for isolation
Indication of three positions: I (ON), Tripped and O (OFF)
Access to the “push-to-trip” button
Visibility of, and access to, trip unit settings
The circuit breaker may be locked in the OFF position by using one to three
padlocks (not supplied)
Models
Standard with black handle
VDE type with red handle and yellow bezel for machine tool control
Variations
Accessories transform the standard direct rotary handle for the following situations:
Motor control centers (MCCs):
– Opening of door prevented when circuit breaker is on
– Closing of circuit breaker inhibited when door is open
Machine tool control; complies with CNOMO E03.81.501N; degree of protection IP54
Early make or early break contacts may be installed into direct mount rotary handle
Standards
The directly-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561
I/ON
(Closed)
Tripped
O/OFF
(Open)
Door Mounted Rotary
Operating Handle
Installation
The door-mounted (extended) rotary operating handle is made up of:
A unit that replaces the front accessory cover of the circuit breaker (secured by screws)
An assembly (handle and front plate) on the door that is always secured in the same position, whether the
circuit breaker is installed vertically or horizontally
An adjustable extension shaft
The handle mechanism can be used in NEMA 3R and 12 enclosure applications
Operation
The door mounted operating handle makes it possible to operate a circuit breaker installed in an enclosure with
the enclosure door closed. The door mounted operating handle maintains:
Suitability for isolation
Indication of the three positions OFF (O), ON (I) and tripped
Visibility of and access to trip unit settings when the door is open
Degree of protection: IP40 as per IEC 529
Defeatable interlock prevents opening of door when circuit breaker is on
The circuit breaker may be locked in the off position by using one to three padlocks, padlock shackle diameter
0.19–0.31 in. (5–8 mm); padlocks are not supplied; locking prevents opening of the enclosure door
Shaft
Length
The shaft length is the distance between the back of the circuit breaker and the door:
Minimum shaft length is 7.4 in. (185 mm)
Maximum shaft length is 24 in. (600 mm)
Extended shaft length must be adjusted
Models
Standard with black handle
VDE type with red handle and yellow bezel for machine tool control
Variations
For drawout configurations, the extended rotary handle is also available with a telescopic shaft containing two
stable positions
Standards
The door-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561