Section 9—Accessories and Auxiliaries
All PowerPact™ H-, J-, and L-frame circuit breakers and automatic switches have slots for the
electrical auxiliaries .
Circuit breakers equipped with Micrologic™ trip units may be equipped with a fault-trip indication to
identify the type of fault by installing
one indication module with two outputs (see page 119)
either an SDx module with Micrologic 3.x / 5.x A or E / 6.x A or E
or an SDTAM module with Micrologic 2.x M.
This module occupies the slots of one auxiliary switch (OF) contact and an undervoltage trip
(MN)/shunt trip (MX).
All these auxiliaries may be installed with a motor operator.
Communication Network
Communication networks require specific auxiliaries.
Communication of status indications:
1 BSCM module
1 NSX cord (internal terminal block) for both communication and 24 Vdc supply to the BSCM.
Communication of status conditions is compatible with a standard motor operator.
Communication of status indications and controls requires, in addition to the previous auxiliaries:
1 communicating motor operator connected to the BSCM.
Communication of measurements is available on Micrologic 5/6. The system consists of:
1 NSX cord (internal terminal block) for both communication and 24 Vdc supply to the Micrologic.
Communication of measurements is compatible with a standard or communicating motor operator.
Communication of status indications, controls and measurements is available on Micrologic 5/6. The
system consists of:
1 BSCM module
1 NSX cord (internal terminal block) for both communication and 24 Vdc supply to the BSCM and
the Micrologic
1 communicating motor operator connected to the BSCM.
Installation of SDx or SDTAM is compatible with communication network.
H- and J-Frame L-Frame
4 indication contacts
2 ON/OFF (auxiliary switches [OF1 and
OF2])
1 trip indication (alarm switch [SD])
1 fault-trip indication (overcurrent trip
switch [SDE])
one remote-tripping release
either 1 undervoltage trip (MN)
or 1 shunt trip (MX)
5 indication contacts
3 ON/OFF auxiliary switches (OF1, OF2,
and OF3)
1 trip indication (alarm switch [SD])
1 fault-trip indication (overcurrent trip
switch [SDE])
one remote-tripping release
either 1 undervoltage trip (MN)
or 1 shunt trip (MX)