Technical Data Bulletin

6-8
© 2020 Schneider Electric
All Rights Reserved
Nipple-Mounted SPDs XDSE Surge Protective Devices
www.se.com/us
Refer to Catalog 6671CT9701
Surgelogic™ Type XDSE Surge Protective Devices
XDSE Series
Surgelogic
TM
XDSE surge protective devices feature a compact design that allows surge
suppression to be externally installed adjacent to electrical distribution equipment. XDSE
systems are designed to provide high-quality surge suppression for a wide variety of
commercial, industrial or institutional applications. XDSEs incorporate patented
overvoltage technology innovations that provide superior overvoltage withstand
capability for systems with unstable power, without compromising transient clamping
performance.
US and Canadian UL Listed to the UL 1449 standard. Complies with requirements of
NEC Article 285 and CSA 22.2 269.1 and 269.2 as appropriate. Complies with UL 96A
12
th
Edition Master Label requirements for Lightning Protection Systems
LED light indicates operation status
Short circuit current rating up to 200 kA
Suitable for indoor and outdoor applications (NEMA Type 4X rated)
Convenient lug connection inside enclosure
-50db EMI/RFI filtering
Audible alarm
Dry contacts
Optional flush mount kit: XDSEMKF
Table 6.6: XDSE Surge Protective Devices
Voltage
Surge Current
per Phase
Modes of
Protection
Configuration
Model Number MCOV l
n
L-N L-G L-L N-G
120/240V 100 6
1Ø, 3–wire + ground SSP01XDSE10A( )
150V 20 kA 700V 700V 600V 1000V
208Y/120V [1]
100 10
3Ø, WYE, 4–wire + ground SSP02XDSE10A( )
150V 20 kA 700V 700V 600V 1000V
240/120 HLD 100 10
3Ø, HLD[2], 4–wire + ground SSP03XDSE10A( )
150/320V 20 kA 700/1200V 700V 600V 1000/2000V
480Y/277V [3]
100 10
3Ø, Wye, 4–wire + ground SSP04XDSE10A( )
320V 20 kA 1200V 1200V 1200V 2000V
480V Delta [4]
100 6
3Ø, Delta, 3–wire + ground SSP05XDSE10A( )
552V 20 kA N/A 1800V N/A 2000V
240V Delta 100 6
3Ø, Delta, 3–wire + ground SSP06XDSE10A( )
300/320V 20 kA N/A 320 V 300 V N/A
600Y/347V 100 10
3Ø, WYE, 4–wire + ground SSP08XDSE10A( )
420V 20 kA 1500V 1500V 1500V 2500V
600V Delta [5]
100 6
1Ø, 3–wire + ground SSP09XDSE10A( )
690V 20 kA N/A 2500V 2500V N/A
120/240 V 150 6
1Ø, 3–wire + ground SSP01XDSE15A( )
150V 20 kA 700V 700V 600V 1000V
208Y/120V [1]
150 10
3Ø, WYE, 4–wire + ground SSP02XDSE15A( )
150V 20 kA 700V 700V 600V 1000V
120/240V HLD 150 10
3Ø, HLD[2], 4–wire + ground SSP03XDSE15A( )
150/320V 20 kA 700/1200V 700/1200V 600V 1000/2000V
480Y/277V [3]
150 10
3Ø, WYE, 4–wire + ground SSP04XDSE15A( )
320V 20 kA 1200V 1200V 1200V 2000V
480V Delta [4]
150 6
3Ø, Delta, 3–wire + ground SSP05XDSE15A( )
552V 20 kA N/A 1800V N/A 2000V
240V Delta 150 6
3Ø, Delta, 3–wire + ground SSP06XDSE15A( )
300/320V 20 kA N/A 320V 300V N/A
600Y/347V 150 10
3Ø, WYE, 4–wire + ground SSP08XDSE15A( )
420V 20 kA 1500V 1500V 1500V 2500V
120/240V 200 6
1Ø, 3–wire + ground SSP01XDSE20A( )
150V 20 kA 700V 700V 600V 1000V
208Y/120V [1]
200 10
3Ø, WYE, 4–wire + ground SSP02XDSE20A( )
150V 20 kA 700V 700V 600V 1000V
240/120 HLD 200 10
3Ø, HLD[2], 4–wire + ground SSP03XDSE20A( )
150/320V 20 kA 700/1200V 700V 600V 1000/2000V
480Y/277V [3]
200 10
3Ø, Wye, 4–wire + ground SSP04XDSE20A( )
320 V 20 kA 1200V 1200 V 1200V 2000 V
480V Delta [4]
200 6
3Ø, Delta, 3–wire + ground SSP05XDSE20A( )
552V 20 kA N/A 1800V N/A 2000V
240V Delta 200 6
3Ø, Delta, 3–wire + ground SSP06XDSE20A( )
300/320V 20 kA N/A 320V 300V N/A
600Y/347V 200 10
3Ø, WYE, 4–wire + ground SSP08XDSE20A( )
420V 20 kA 1500V 1500V 1500V 2500V
( ) For a Type 1 SPD, add a “1” suffix to the catalog number.
6
SURGE PROTECTIVE DEVICES
(SPDS)
[1] 208Y/120 series also applies to the following voltage 220Y/127.
[2] HLD= High-leg delta.
[3] 480Y/277 series also applies to the following voltages 380Y/220, 400Y/230, and 415Y/240.
[4] 480V Delta series also applies to the following voltage 480Y/277V HRG.
[5] 600 V Delta series also applies to the following voltages 600Y/347V HRG.
1/17/2020