Technical Data Bulletin
© 2020 Schneider Electric
All Rights Reserved
6-7
www.se.com/us
Internally Mounted SPDs—Retrofit/Ready
to Install
Internally Mounted SPDs
Refer to Catalog 6671CT9701
OEM/Assembler Kits
OEM Kit
Surgelogic™ OEM/assembler kits allow manufacturers to add industry-leading surge
suppression directly to customized equipment. Manufacturers benefit from shorter wire
lengths that optimize the clamping voltage of the SPD. Products come with a backplane-
mounted SPD, mounting hardware and diagnostic display with 36-inch cables. Audible
alarm, silence switch, remote monitoring contacts, and surge counter are standard.
Available as UL 1449 Type 2 (or 1 with optional suffix in catalog number).
US and Canadian UL
®
Recognized to UL 1449 and UL 1283 standards. Complies with
requirements of NEC
®
Article 285 and CSA 22.2 No. 8-M1986 as appropriate. Complies
with UL 96A 12th Edition Master Label requirements for Lightning Protection Systems.
Table 6.5: OEM/Assembler Kits
Service
Voltage
Peak Surge Current Rating
per Phase (kA)
Cat. No. [13]
120/240 V, 1-phase,
3-wire + ground
120
TVS1IMA12O( )
160
TVS1IMA16O( )
240
TVS1IMA24O( )
208Y/120 V, 3-phase,
4-wire + ground [14] [15]
Wye
120
TVS2IMA12O( )
160
TVS2IMA16O( )
240
TVS2IMA24O( )
240/120 V, 3-phase,
4-wire + ground
High-leg Delta
120
TVS3IMA12O( )
160
TVS3IMA16O( )
240
TVS3IMA24O( )
240 V, 3-phase,
3-wire + ground [14] [16]
Delta
120
TVS6IMA12O( )
160
TVS6IMA16O( )
240
TVS6IMA24O( )
480Y/277 V, 3-phase,
4-wire + ground [14] [16]
Wye
120
TVS4IMA12O( )
160
TVS4IMA16O( )
240
TVS4IMA24O( )
480 V, 3-phase,
3-wire + ground [17]
Delta
120
TVS5IMA12O( )
160
TVS5IMA16O( )
240
TVS5IMA24O( )
600Y/347 V, 3-phase,
4-wire + ground [14]
Wye
120
TVS8IMA12O( )
160
TVS8IMA16O( )
240
TVS8IMA24O( )
600 V, 3-phase,
3-wire + ground [18]
Delta
120
TVS9IMA12O( )
160
TVS9IMA16O( )
180
TVS9IMA18O( )
( ) For a Type 1 SPD, add a “1” suffix to the catalog number.
6
SURGE PROTECTIVE DEVICES
(SPDS)
[13] Note the last character of the catalog number is the letter “O”, not a zero.
[14] Can be used on 4-wire or 3-wire grounded wye systems with or without neutral.
[15] 208Y/120 series also applies to the following voltage 220Y/127.
[16] 480Y/277 series applies to the following voltages 380Y/220, 400Y/230, and 415Y/240.
[17] 480 V Delta series also applies to the following voltage: 480Y/277V HRG.
[18] 600 V Delta series also applies to the following voltage: 600Y/347V HRG.
1/17/2020