Technical Data Bulletin
6-10
© 2020 Schneider Electric
All Rights Reserved
Nipple-Mounted SPDs SDSA1175 and SDSA 3-Phase SPDs
www.se.com/us
Refer to Catalog 6671CT9701
SDSA1175 and SDSA 3-Phase Surge Protective Devices
SDSA1175
SDSA 3-Phase
Surgelogic
TM
SDSA1175 surge protective devices are designed and listed for indoor or
outdoor installation and surge suppression for single-phase three-wire 120/240 Vac or
two-wire 120 Vac 60 Hz electrical services. This product is ideal for panel builders as well
as manufacturers and integrators of instrumentation cabinets for industrial and
commercial applications for single-phase power systems. Two SDSA1175 surge
protection devices can be installed to provide suppression for 208Y/120 Vac three-phase
four-wire services.
Surgelogic
TM
SDSA 3-Phase surge protective devices are designed and listed for indoor
or outdoor installation and surge suppression for three-phase electrical services up to
600 Vac. The SDSA 3-Phase series is used extensively in service entrance panels to
provide an efficient and economical means of surge suppression and also ideal for point
of use applications for that added level of protection.
US and Canadian UL
®
Listed as Type 1 SPD to the UL 1449 standard. Complies with
requirements of NEC
®
Article 285, CSA 233.1-87, and CSA C22.2 No. 8-M1986 as
appropriate.
•
LED indicates operational status
•
Short circuit current rating 25 kA (SDSA1175), 200 kA (SDSA 3-Phase)
•
Suitable for indoor and outdoor applications (NEMA Type 4X rated)
•
Convenient back-nipple mounting
•
Optional mounting bracket QOSAMK (for SDSA1175/SDSA1175T)
Table 6.9: SDSA1175 and SDSA 3-Phase Surge Protective Devices
System Voltage
Peak Surge
Current Rating
per Phase (kA)
Cat. No.
SDSA1175
120/240 V, 1-phase, 3-wire
36 SDSA1175
120 V, 1-phase, 2-wire
36 SDSA1175T
SDSA 3-Phase
208Y/120 V,
3-phase, 4-wire [10] [11]
40 SDSA2040
240 V Delta,
3-phase, 3-wire [12]
40 SDSA2040D
480Y/277 V,
3-phase, 4-wire [13] [10]
40 SDSA4040
480 V Delta,
3-phase, 3-wire
40 SDSA4040D
600Y/347 V,
3-phase, 4-wire [10]
40 SDSA3650
600 V Delta,
3-phase, 3-wire
40 SDSA3650D
6
SURGE PROTECTIVE DEVICES
(SPDS)
[10] Do not use on ungrounded systems. Systems must be solidly grounded.
[11] Applicable voltages: 220Y/127V, 208Y/120V.
[12] Applicable voltages: 240V Delta, 240/120V High-Leg Delta.
[13] Applicable voltages: 480Y/277V, 415Y/240V, 400Y/230V, 380Y/220V.
1/17/2020