Brochure

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Short-Circuit Current Ratings
9
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
UL 508 Group Motor Installations
Manual Combination Motor Controller, TeSys
®
GV
GV2ME: UL File E164864
(MC 164581, Report 1012350, Project 2152063)
Table 6: TeSys GV2ME Horsepower and SCCR Ratings
In association with LC1D contactors, suitable for group installation when protected by fuses or an inverse-time
circuit breaker (when used with GV1G09 terminal or GV2G05 blocks plus GV2G busbars)
Standard Motor Ratings @ 50/60 Hz (hp)
Associated
Cable,
AWG
75 °C, Cu
Manual
Motor
Starter
Overload
Trip
Range
(A)
SCCR (kA)
1 Ø 3 Ø
Contactor
240/
480 V
600Y/
347 V
480 V
with
GV1L3
Limiter
Contactor
600 V with
LA9LB920
Limiter
120 V 240 V 200 V 240 V 480 V 600 V
10 GV2ME01 0.1–0.16
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
10 GV2ME02 0.16–0.25
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
10 GV2ME03 0.25–0.4
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
10 GV2ME04 0.4–0.63
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
0.5 10 GV2ME05 0.63–1
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
0.75 10 GV2ME06 1–1.6
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
0.5 0.5 1 10 GV2ME07 1.6–2.5
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
0.75 1 2 10 GV2ME08 2.5–4
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
1.5 1.5 4 10 GV2ME10 4–6.3
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
0.5 1 2 3 5 7.5 10 GV2ME14 6–10
LC1D09 or
D12
65 42 65
LC1D09 or
D12
42
123310108 GV2ME16 9–14
LC1D12 or
D18
22 10 65
LC1D32 or
D38
42
135510158 GV2ME20 13–18
LC1D12 or
D18
22 10 65
LC1D32 or
D38
42
2357.515206 GV2ME21 17–23
LC1D25 or
D32
10 10 65
LC1D32 or
D38
42
2357.515206 GV2ME22 20–25
LC1D25 or
D32
10 10 65
LC1D32 or
D38
42
2 5 10 10 20 30 6 GV2ME32 24–32
LC1D25 or
D32
5565
LC1D32 or
D38
42