GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Short-Circuit Current Ratings
© 2001–2010 Schneider Electric
All Rights Reserved
8
6/2010
UL 508 Type F
Combination Motor Controller, TeSys
®
GV
Manual Self-Protected Combination Starter Meeting UL 508 Type F, UL File E164871
Table 4: TeSys GV2P Horsepower and SCCR Ratings
In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars
(multiple starters)
Standard Motor Ratings @ 50/60 Hz (hp)
Associated
Cable, AWG
75 °C, Cu
Manual
Self-Protected
Starter
Overload Trip
Range (A)
Type of
Contactor
Required
SCCR (kA)
480Y/277 V
1 Ø 3 Ø
120 V 240 V 200 V 240 V 480 V 600 V
10 GV2P01 0.1–0.16 LC1D09 or D12 100
10 GV2P02 0.16–0.25 LC1D09 or D12 100
10 GV2P03 0.25–0.4 LC1D09 or D12 100
10 GV2P04 0.4–0.63 LC1D09 or D12 100
0.5 10 GV2P05 0.63– 1 LC1D09 or D12 100
0.75 10 GV2P06 1–1.6 LC1D09 or D12 100
0.5 0.5 1 10 GV2P07 1.6–2.5 LC1D09 or D12 100
0.75 1 2 10 GV2P08 2.5– 4 LC1D09 or D12 100
1.5 1.5 4 10 GV2P10 4–6.3 LC1D09 or D12 100
0.512357.510 GV2P14 6–10 LC1D09 or D12 100
123310108 GV2P16 9–14 LC1D12 or D18 42
135510158 GV2P20 13–18 LC1D12 or D18 42
2357.515206 GV2P21 17–23 LC1D25 or D32 42
2357.515206 GV2P22 20–25 LC1D25 or D32 42
Table 5: TeSys GV3P Horsepower and SCCR Ratings
In combination with line spacer GV3G66 and magnetic trip unit GVAM11 for stand-alone starters
Standard Motor Ratings @ 50/60 Hz (hp)
Associated
Cable,
AWG
75 °C, Cu
Manual
Self-Protected
Starter
Overload
Trip Range
(A)
Type of Contactor
Required
SCCR (kA)
1 Ø 3 Ø
480Y/
277 V
600Y/
347 V
120 V 240 V 200 V 240 V 480 V 600 V
12337.5108 GV3P13 9–13 LC1D18 65 25
13357.5108 GV3P18 12–18 LC1D18 65 25
2 3 5 7.515206 GV3P25 17–25 LC1D25 65 25
2 3 7.57.520256 GV3P32 23–32 LC1D32 65 25
3 5 101025303 GV3P40 30–40 LC1D40A/ 50A/65A 65 25
3 7.5 10 10 30 40 3 GV3P50 37–50 LC1D50A/65A 65 25
5 10151540503 GV3P65 48–65 LC1D65A/80 65 25