Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Short-Circuit Current Ratings
7
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
Short-Circuit Current Ratings
UL 508 Type E
Manual Self-Protected Combination Motor Controller, TeSys
®
GV
Manual Self-Protected Combination Starter Meeting UL 508 Type E, UL File E164871
Table 2: TeSys GV2P Horsepower and SCCR Ratings
In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars
(multiple starters)
Standard Motor Ratings @ 50/60 Hz (hp)
Associated
Cable,
AWG 75 °C, Cu
Manual
Self-Protected
Starter
Overload Trip
Range (A)
SCCR (kA)
480Y/277V
1 Ø 3 Ø
120 V 240 V 200 V 240 V 480 V 600 V
10 GV2P01 0.1–0.16 100
10 GV2P02 0.16–0.25 100
10 GV2P03 0.25–0.4 100
10 GV2P04 0.4–0.63 100
0.5 10 GV2P05 0.63–1 100
0.75 10 GV2P06 1–1.6 100
0.5 0.5 1 10 GV2P07 1.6–2.5 100
0.75 1 2 10 GV2P08 2.5–4 100
1.5 1.5 4 10 GV2P10 4–6.3 100
0.512357.510 GV2P14 6–10 100
1 2 3 3 10 10 8 GV2P16 9–14 10
1 3 5 5 10 15 8 GV2P20 13–18 10
2 3 5 7.5 15 20 6 GV2P21 17–23 10
2 3 5 7.5 15 20 6 GV2P22 20–25 10
Table 3: TeSys GV3P Horsepower and SCCR Ratings
In combination with line spacer GV3G66 and magnetic trip unit GVAM11 for stand-alone starters
Standard Motor Ratings @ 50/60 Hz (hp)
Associated
Cable, AWG
75 °C, Cu
Manual
Self-Protected
Starter
Overload Trip
Range (A)
SCCR (kA)
1 Ø 3 Ø
480Y/277 V 600Y/347 V
120 V 240 V 200 V 240 V 480 V 600 V
12337.5108 GV3P13 9–13 100 25
13357.5108 GV3P18 12–18 100 25
2357.515206 GV3P25 17–25 100 25
237.57.520256 GV3P32 23–32 100 25
3 5 101025303 GV3P40 30–40 65 25
3 7.5 10 10 30 40 3 GV3P50 37–50 65 25
5 10151540503 GV3P65 48–65 65 25