Brochure

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Mounting Dimensions and Wiring Diagrams
59
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
GV7 Mounting Dimensions
Motor Controllers
GV7R
Motor Controllers with Terminal Shields and Phase Barriers
GV7R + GV7AC01 + GV7AC04
1. 126 for GV7R 220 2. Phase barriers—GV7AC04
3. Terminal shields—GV7AC01
Safety Clearance x1 x2
in. (mm) in. (mm)
Painted or insulated metal plate, insulation, or
insulated bar
0 (0) 1.18 (30)
Bare metal plate
U 440 V 0.20 (5) 1.38 (35)
440 V < U < 600 V 0.39 (10) 1.38 (35)
U 600 V 0.79 (20) 1.38 (35)
Minimum distance between two manual motor starters mounted side by side = 0.
Combination of GV7 and LC1F with Kit GV7AC0 in. (mm)
abc
GV7R + LC1F115 or
F150 + GV7AC06
4.69 (119) 13.15 (334) 7.13 (181)
GV7R + LC1F185 +
GV7AC06
4.69 (119) 13.31 (338) 7.40 (188)
GV7R + LC1F225 +
GV7AC07
5.16 (131) 14.09 (358) 7.40 (188)
GV7R + LC1F265 +
GV7AC07
5.12 (130) 14.33 (364) 8.46 (215)
3.19
81
3.39
86
4.37
111 (1)
=
6.34
161
=
=
=
4.92
125
=
4.13
105
==
1.38
35
=
=
12.64
321
=
3.19
81
=
=
==
==
6.34
161
==
14.06
357
(2)
(3)
x1
x1
x2x2
ac
b
Dimensions:
in.
mm