GV3 Mounting Dimensions
Dimensions
X1 = Electrical clearance (ISC max)
40 mm for Ue < 500 V, 50 mm for Ue < 690 V
1. Blocks GVAN••, GVAD•• and GVAM11
2. Blocks GV3AU
•• and GV3AS••
The GV3G66 add-on line terminal shroud must be
installed on the GV3P for it to meet UL 508 Type E
requirements for standalone applications. The shield
snaps into place on the line side of the GV3P.
NOTE: Between two manual motor starters, leave a 9 mm gap, either an empty space or side-mounting add-on contact blocks.
Horizontal mounting is possible up to 40 °C.
NOTE: If the GV3G66 add-on line terminal shroud is installed, the GV3G busbars cannot be installed.
Mounting
Mounting with TeSys Contactor LC1D40A–D65A
Side-by-Side Mounting
(S-shape Busbar System GV3S)
Mounting on Rail AM1DE200 or AM1ED201 Panel Mounting, using M4 Screws Mounting on Pre-Slotted Plate AM1 PA
Busbar Systems
Set of Busbars GV3G264 Set of Busbars GV3 G364
NOTE: Between two manual motor starters, leave a 9 mm gap, either an empty space or side-mounting add-on contact blocks. Horizontal mounting is possible up to 40 °C.
NOTE: If the GV3G66 add-on line terminal shroud is installed, the GV3G busbars cannot be installed.
X1
X1
5.35
136
2.52
64
2.68
68
2.17
55
5.2
132
(2)
(1)
0.35
9
0.71
18
GV3G66 Shroud
3.94
100
0.45
11.4
2.5
63.55
5.73
145.5
1.89
47.9
5.35
136
2.17
55
4.72
120
9.09
231
5.35
136
5.43
138
4.69
119
5.67
144
2.52
64
2.68
68
3xØ4
5.35
136
1.48
37.5
5.41
137.5
AF1EA4
5.35
136
0.74
18.7
0.74
18.7
5.41
137.5
4.69
119
0.63
16
7.2
183
0.63
16
Dimensions:
in.
mm