Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Selection
51
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
Magnetic Fault Indicators
The magnetic fault indicator does one of the following:
• differentiates a thermal fault from a magnetic fault
• opens the contactor only in the event of a thermal fault (see page 50)
Undervoltage Trip Units, GV7AU
The undervoltage trip opens the motor starter when the control voltage drops below the trip threshold
of 0.35–0.7 times the rated voltage. The starter contacts close again when the control voltage rises
above 0.85 times the rated voltage. The GV7AU undervoltage trip unit meets the requirements of
IEC 60947-2. For the location of the undervoltage trip unit, see Figure 5 on page 50.
Shunt Trip Units, GV7AS
The shunt trip opens the motor starter when the control voltage rises above 0.7 times the rated
voltage. For location of the shunt trip unit, see Figure 5 on page 50.
Trip Unit Operation, GV7AU or GV7AS
When the motor starter has been tripped by a GV7AU or AS trip unit, it must be reset either locally or
by remote control. For information on remote control, consult your local sales office.
Tripping has priority over manual closing. When a trip condition is present, manual action does not
close the contacts, even temporarily.
Table 62: Magnetic Fault Indicators
Voltage Catalog Number Weight, lb (kg)
24–48 Vac / 24–72 Vdc GV7AD111
0.22 (0.100)
110–240 Vac/Vdc GV7AD112
Table 63: Undervoltage Trip and Shunt Trip Devices
Type Voltage Catalog Number Weight, lb (kg)
Undervoltage trip
48 V, 50 Hz GV7AU055 0.23 (0.105)
110–130 V, 50/60 Hz GV7AU107
0.24 (0.110)
200–240 V, 50/60 Hz GV7AU207
380–440 V, 50/60 Hz GV7AU387 0.23 (0.105)
525 V, 50 Hz GV7AU525 0.22 (0.100)
Shunt trip
48 V, 50 Hz GV7AS055 0.23 (0.105)
110–130 V, 50/60 Hz GV7AS107
0.24 (0.110)
200–240 V, 50/60 Hz GV7AS207
380–440 V, 50/60 Hz GV7AS387 0.23 (0.105)
525 V, 50 Hz GV7AS525 0.22 (0.100)