Brochure
© 2001–2010 Schneider Electric
All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Selection
50
6/2010
Auxiliary Contacts
Auxiliary contacts remotely indicate the state of the contacts in the starter. The auxiliary contacts can
be used for signaling, electrical locking, or relaying. Standard and low-level versions are available. The
auxiliary contacts include a terminal block. A hole is provided for wiring exit.
An auxiliary contact can perform any of the functions listed in Table 60, depending on where the
contact is located in the starter.
Figure 5: Auxiliary Contact Locations
Table 60: Auxiliary Contact Location and Function
Location Function Application
1 N.O./N.C. contact Indicates the position of the starter poles.
2 Trip indicator
Indicates that the starter has tripped due to an overload, short circuit, differential fault
condition, the operation of a voltage release (undervoltage or shunt release), or from
pressing the push-to-trip button. The trip indicator resets when the starter is reset.
3
Electrical fault
indicator
Indicates that the starter has tripped due to an overload, short circuit, or differential fault.
The electrical fault indicator resets when the starter is reset.
4 N.O./N.C. contact Indicates the position of the starter poles.
Table 61: Auxiliary Contacts
Type Voltage Catalog Number Weight, lb (kg)
Standard — GV7AE11
0.03 (0.015)
Low level — GV7AB11
GV7RE, RS
GV7AE11, AB11
GV7AU, AS
GV7AD••
1
2
3
4