Brochure

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Selection
© 2001–2010 Schneider Electric
All Rights Reserved
38
6/2010
GV2 and GV3 Selection
NOTE: For GV2 and GV3 accessories and enclosures, see pages 40–47.
Table 47: GV2 Manual Motor Controller and Protector Horsepower Ratings
Catalog Number
Thermal Trip
Setting Range
(A)
Maximum Horsepower Ratings
Push Button Rotary Handle 1 Ø 3 Ø
GV2ME
[1]
1
For spring terminals, add the numeral 3 to the end of the catalog number. Example: GV2ME013.
GV2P 120 V 208 V 240 V 208 V 240 V 480 V 600 V
[2]
2
GV2P•• is not Type E or Type F.
GV2ME01 GV2P01 0.11–0.16
GV2ME02 GV2P02 0.016–0.25
GV2ME03 GV2P03 0.25–0.40
GV2ME04 GV2P04 0.40–0.63
GV2ME05 GV2P05 0.631 ———————
GV2ME06 GV2P06 1–1.6 0.1 0.75 0.75
GV2ME07 GV2P07 1.6–2.5 0.16 0.16 0.5 0.5 1 1.5
GV2ME08 GV2P08 2.5–4 0.125 0.25 0.33 0.75 0.75 2 3
GV2ME10 GV2P10 4–6.3 0.25 0.5 0.5 1 1.5 3 5
GV2ME14 GV2P14 610 0.511.52 3 57.5
GV2ME16 GV2P16 9–14 0.75 2 2 3 3 10 10
GV2ME20 GV2P20 13–18 1 2 3 5 5 10 15
GV2ME21 GV2P21 17–23 1.5 3 3 5 7.5 15 20
GV2ME22 GV2P22 20–25 2 3 7.5 15 20
GV2ME32
[3]
3
GV2ME32 is not available with spring terminals.
GV2P32 24–32 2 5 5 7.5 10 20 25
File LR 81630
Class 3211 05
File E164864
CCN NLRV
Table 48: GV3P Manual Motor Controller and Protector Horsepower Ratings
Catalog Number
Thermal Trip
Setting Range
(A)
Maximum Horsepower Ratings
1 Ø 3 Ø
120 V 240 V 208 V 240 V 480 V 600 V
GV3P13 9–13 0.5 1.5 3 3 7.5 10
GV3P18 12–18 0.75 2 3 5 7.5 10
GV3P25 17–25 1.5 3 5 7.5 15 20
GV3P32 23–32 2 3 7.5 7.5 20 25
GV3P40 30–40 3 5 10 10 25 30
GV3P50 37–50 3 7.5 10 10 30 40
GV3P65 48–65 3 10 15 15 40 50
GV2ME GV2ME••3 GV2P GV3P