Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Selection
37
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
Selection
Fuse and Circuit Breaker Selection
When selecting the proper upstream short circuit protection for Group Motor installations, you must
apply the specific rules of the National Electrical Code (NEC) for Group Motor installations. To help
clarify this process, below are examples of how to choose the correct GV manual starter and the
proper size short circuit protection for an application. These examples illustrate the most common
applications of GV manual starters with upstream short circuit protection in a Group Motor installation.
Refer to NEC section 430-53C and section 430-53D for proper conductor ampacity selection.
NOTE: The examples below show full-load ampere (FLA) ratings that may not be typical. Use the
motor nameplate data to determine actual values.
Example 1: Eight motors with the sizes shown in Table 45 are installed on a conveying system. Time-delay fuses
are used.
In accordance with NEC section 430-52, section 430-53, and table 430-152, the time-delay fuse must
be sized as follows:
175% FLA for largest motor + sum of FLAs for all other motors
⇒ (1.75 x 7.6) + (2 x 4.8) + (5 x 3.4) = 39.9 A
NEC 430-52 allows use of the next largest standard-size fuse—which in this case is 40 A. If nuisance
tripping is a problem with this fuse selection, NEC does allow 225% of the largest motor FLA to be
used in lieu of 175% when calculating the size. In this case, the calculation is as follows (the next
largest standard fuse size in this case is 45 A):
(2.25 x 7.6) + (2 x 4.8) + (5 x 3.4) = 43.7 A
Example 2: Ten motors with the sizes shown in Table 46 are installed on a packaging machine. Choose the proper
size inverse-time circuit breaker for this application.
In accordance with NEC section 430-52, section 430-53, and NEC table 430-152, the inverse-time
circuit breaker must be sized as follows (the next largest standard-size inverse-time circuit breaker
is 90 A):
250% FLA for largest motor + sum of FLAs for all other motors
⇒ (2.5 x 14) + 14 +7.6 + (2 x 4.8) + (5 x 3.4) = 83.2 A
If nuisance tripping is a problem, the NEC allows for inverse-time circuit breaker sizes that “shall in no
case exceed 400% for full-load currents of 100 amps or less, or 300% for full-load current greater than
100 amps.” In this case, the calculation is as follows (the next largest standard inverse-time circuit
breaker size in this case is 110 A):
(4.0 x 14) + 14 +7.6 + (2 x 4.8) + (5 x 3.4) = 104.2 A
Disconnect
Fuse or
Circuit Breake
r
GV2 Manual Motor Starter
TeSys D or TeSys K
Contactor
Motor
Table 45: Example 1—Motor Sizes
Motor Quantity Rating (hp) Voltage FLA Starter Selected
154607.6GV2ME14
234604.8GV2ME10
524603.4GV2ME08
Table 46: Example 2——Motor Sizes
Motor Quantity Rating (hp) Voltage FLA
2 10 460 14
1 5 460 7.6
2 3 460 4.8
5 2 460 3.4