Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
29
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
GV7 Auxiliary Contact Specifications
Table 33: Auxiliary Contact Characteristics
Type of contacts GV7AE11 GV7AB11
Rated insulation voltage (Ui)
(associated insulation
coordination)
Conforming to IEC 60947-1 from
CSA C22.2 No. 14 and UL 508
V 690 690
Conventional thermal current
(Ith)
Conforming to IEC 60947-5-1 from
CSA C22.2 No. 14 and UL 508
A 66
Mechanical durability
(C.O.: Close - Open)
C.O. 50 000 50 000
Operational current—
AC operation
Conforming to IEC 60947-5-1
Rated operational
voltage (Ue)
AC-12 or AC-15. 50,000 C.O. AC-12 or AC-15. 50,000 C.O.
V 2448110
230/
240
380/
415
440 690 24 48 110
230/
240
380/
415
440 690
Rated operational
current (Ie)
AC-12 A 66666665555555
AC-15 A 6654330.155432.52.50.1
Operational current—
DC operation
Conforming to IEC 60947-5-1
Rated operational
voltage (Ue)
DC-12 or DC-14. 50,000 C.O. DC-12 or DC-14. 50,000 C.O.
V 24 48 110 250 24 48 110 250
Rated operational
current (Ie)
DC-12 A 2.5 2.5 0.8 0.3 2 2 0.5 —
DC-14 A 1 0.2 0.5 0.03 0.5 0.1 0.25 —
Minimum operational conditions—
DC operation
V 17 12
mA 55
Short-circuit protection
GB2CB•• circuit breaker
(rating according to operational current for Ue ≤ 415 V) or gG fuse, 10 A maximum.
Cabling
Solid cable mm
2
1 x 1.5 conductor (1 x 16 AWG) 1 x 1.5 conductor (1 x 16 AWG)
Flexible cable without cable end mm
2
1 x 1.5 conductor (1 x 16 AWG) 1 x 1.5 conductor (1 x 16 AWG)
Flexible cable with cable end mm
2
1 x 1.5 conductor (1 x 16 AWG) 1 x 1.5 conductor (1 x 16 AWG)
Table 34: Electrical Characteristics
Type GV7AU or GV7AS
Rated insulation voltage (Ui) conforming to IEC 60947-1 690 V
Operational voltage conforming to IEC 60947-1 0.85–1.1 Ue (V)
Drop-out voltage 0.35–0.7 Ue (V)
Inrush consumption
<10 VA
<5 W
Sealed consumption
<5 VA
<5 W
Operating time conforming to IEC 60947-1 <50 ms
On-load factor 100%
Cabling, solid or flexible cable 2 x 16 AWG (2 x 1.5 mm
2
) maximum