Table 31: Technical Characteristics
Type
GV7
RE20–RE100 RS40–RS100 RE150 RS150 RE220 RS220
Utilization category
Conforming to
IEC 60947-2
AAA
Conforming to
IEC 60947-4-1
AC-3 AC-3 AC-3
Rated operational voltage (Ue) conforming to IEC 60947-2 690 V 690 V 690 V
Rated insulation voltage (Ui) conforming to IEC 60947-2 750 V 750 V 750 V
Rated voltage conforming to CSA C22.2 No. 14, UL 508 600 V 600 V 600 V
Rated operational frequency
[1]
conforming to IEC 60947-2 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse withstand voltage (U imp)
conforming to IEC 60947-2
8 kV 8 kV 8 kV
Total power dissipated per pole 5 W 8.7 W 14.5 W
Electrical durability
(C.O. = close-open cycles)
440 V In/2 50,000 C.O. 40,000 C.O. 20,000 C.O.
440 V In 30,000 C.O. 20,000 C.O. 10,000 C.O.
Rated duty, conforming to IEC 60947-4-1 Continuous duty Continuous duty Continuous duty
Type
GV7
RE40–RE100 RS40–RS100 RE150 RS150 RE220 RS220
Rating 25–40 A to 60–100 A 90–150 A 90–150 A 132–220 A 132–220 A
Breaking capacity
conforming to IEC 60947-2
230/240 V
Icu
[2]
85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
Ics%
[3]
100% 100% 100% 100% 100% 100%
400/415 V
Icu
[2]
25 kA 70 kA 35 kA 70 kA 35 kA 70 kA
Ics%
[3]
100% 100% 100% 100% 100% 100%
440 V
Icu
[2]
25 kA 65 kA 35 kA 65 kA 35 kA 65 kA
Ics%
[3]
100% 100% 100% 100% 100% 100%
500 V
Icu
[2]
18 kA 50 kA 30 kA 50 kA 30 kA 50 kA
Ics%
[3]
100% 100% 100% 100% 100% 100%
690 V
Icu
[2]
8 kA 10 kA 8 kA 10 kA 8 kA 10 kA
Ics%
[3]
100% 100% 100% 100% 100% 100%
1
GV7R motor controllers and protectors are not recommended for use with variable speed controllers or soft start units in applications under 40 Hz.
2
Icu = interrupting capacity at full voltage.
3
Ics = short-circuit interrupting capacity as a percentage of Icu.
Table 32: UL Maximum SCCR (rms) (kA)
[1, 2]
1
Group Installation: Maximum NTD fuse size: 1200 A. Maximum manual starter and protector rating: 1200 A.
2
Suitable for use on a circuit with an available SCCR no greater than the SCCR of the manual motor controller or manual starter
and protector, whichever is less.
Type Range
SCCR
240 V
[3]
3
Nominal system voltage.
480 V
[3]
600 V
[3]
GV7RE40 25–40 A 25 25 10
GV7RE50 30–50 A 25 25 10
GV7RE80 48–80 A 25 25 10
GV7RE100 60–100 A 25 25 10
GV7RE150 90–150 A 25 25 10
GV7RE220 132–220 A 25 25 10
GV7RS40 25–40 A 65 65 10
GV7RS50 30–50 A 65 65 10
GV7RS80 48–80 A 65 65 10
GV7RS100 60–100 A 65 65 10
GV7RS150 90–150 A 65 65 10
GV7RS220 132–220 A 65 65 10