Brochure

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
27
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
GV7 Specifications
Table 29: Environment
Conforming to standards
IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, 60947-4-1,
NF C 63-650, 63-120, 79-130, VDE 0113, UL 508, CSA C22.2 No.14
Approvals
UL File E 164864 CCN NLRV
CSA File LR 81630 Class 3211 05
Protective treatment
“TC”
Degree of protection
Conforming to IEC 60529
IP405 with terminal shields
Ambient air
temperature
Storage -68 °F to +203 °F (-55 °C to +95 °C)
Operation -13 °F to +158 °F (-25 °C to +70 °C)
Temperature compensation
-13 °F to +130 °F (-25 °C to +55 °C)
For use up to +158 °F (70 °C), consult your local sales office.
Maximum operating altitude
6562 ft. (2000 m)
Operating position
Suitability for isolation
Conforming to IEC 60947-1 7-1-6
Yes
Vibration resistance
2.5 g
n
at 25 Hz
Phase loss sensitivity
Conforming to IEC 60947-4-1, 7-2-1-5-2
Table 30: Cabling Characteristics
Type
Connection by bars or cables
GV7R•40–R•100 GV7R•150 GV7R•220
Pitch
Without spreaders 1.4 in. (35 mm)
With spreaders 1.8 in. (45 mm)
Bars or cables
with lugs
e 0.24 in. (6 mm)
L 1 in. (25 mm)
d 0.39 in. (10mm)
Screws
Size M6 M8
Tightening torque 7.5 lb-ft (10 Nm) 11.3 lb-ft (15 Nm)
Bare cables
(copper or aluminum)
with connectors
Height 0.78 in. (20 mm)
Wire size
16 AWG
(1.5 mm
2
)
16–3/0 AWG
(1.5–95 mm
2
)
16 AWG–350 mcm
(1.5–185 mm
2
)
Tightening torque 11.3 lb-ft (15 Nm)
90° 90° 90° 90°
e
L
d
d
L
h