Brochure

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
23
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
GV3 Auxiliary Contact Specifications
Table 25: Auxiliary Contacts for GV2 and GV3P Manual Motor Starters, Controllers, and Protectors
Type of contacts Units
Instantaneous auxiliary
GVAN, GVAD
Fault signaling
GVAD, GVAM11
Instantaneous
auxiliary GVAE
Rated insulation
voltage (Ui)
(associated insulation
coordination)
Conforming to IEC 60947-1 V 690 690
250 (690 in relation to
main circuit)
Conforming to CSA C22-2 n° 14
and UL 508
V 600 300 300
Conventional
thermal current (Ith)
Conforming to IEC 60947-5-1 A 6 2.5 2.5
Conforming to CSA C22-2 n° 14
and UL 508
A5 1 1
Operational power
and current—
AC operation
Conforming to
IEC 60947-5-1
AC-15/100,000 C.O.
[1]
1
C.O. = close–open operations.
AC-14/1000 C.O.
[1]
AC-15/100,000 C.O.
[1]
Rated operational voltage (Ue) V 48
110
127
230
240
380
415
440 500 690 24 48
110
127
230
240
24 48
110
127
230
240
Operational power,
normal conditions
VA 300 500 720 850 650 500 400 36 48 72 72 48 60 120 120
Occasional breaking and making
capacities, abnormal conditions
kVA3 7 131513129 0.220.30.450.450.480.61.272.4
Rated operational current (Ie) A 6 4.5 3.3 2.2 1.5 1 0.6 1.5 1 0.5 0.3 2 1.25 1 0.5
Operational power
and current—
DC operation
Conforming to
IEC 60947-5-1
DC-13/100,000 C.O.
[1]
DC-13/1000 C.O.
[1]
DC-13/100,000 C.O.
[1]
Rated operational voltage (Ue) V 24 48 60 110
240
[2]
2
Add an RC circuit type LA4 D to the load terminals. Consult the Digest.
24 48 60 24 48 60
Operational power,
normal conditions
W 140 240 180 140 120 24 15 9 24 15 9
Occasional breaking and making
capacities, abnormal conditions
W 240 360 240 210 180 100 50 50 100 50 50
Rated operational current (Ie) A 6 5 3 1.3 0.5 1 0.3 0.15 1 0.3 0.15
Low power switching reliability of contact
(varies with conditions)
GVAE: Number of failures for n million operating cycles (17 V, 5 mA): = 10
-6
Minimum operational conditions—
DC operation
V17
mA 5
Short-circuit protection
GB2CB•• circuit breaker (rated according to operational current for
Ue < 415 V) or via gG fuse 10 A maximum
GB2CB06 or gG fuse
10 A maximum
Cabling, screw
clamp terminals
Number of conductors 1 2
Solid cable mm
2
1–2.5 1–2.5
Flexible cable without cable end mm
2
0.75–2.5 0.75–2.5
Flexible cable with cable end mm
2
0.75–1.5 0.75–1.5
Tightening torque N•m 1.4 maximum 1.4 maximum
Cabling, spring
terminal
connections
GVAN only
Flexible cable without cable end mm
2
0.75–2.5 0.75–2.5 0.75–1.5
Operation of instantaneous auxiliary contacts
Operation of fault signaling contacts
GVAM11
Change of state following trip on short circuit.
GVAD10•• and GVAD01••
Change of state following trip on short circuit,
overload, or undervoltage.
N.O.
N.O.
N.O.
N.C.
N.C.
N.O.
N.O.
N.O.
Power poles:
GVAN11
GVAE1
GVAE20
01
Contact open
Contact closed
GVAN20
N.C.
N.O.
GVAE11
N.O.
GVAD 10
N.C.
GVAD 01