Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
19
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
Table 17: GV2ME Breaking Capacity for European Applications
Type Units
Catalog Number Suffix (GV2ME)
01–06 07 08 10 14 16 20 21 22
Rating
[1]
1
Ics = % of Icu.
A 0.1–1.6 2.5 4 6.3 10 14 18 23 25
Breaking capacity
conforming to IEC 60947-2
230/240 V
Icu
kA
>100 kA
50 50
% 100 100
400/415 V
kA
>100 kA
15 15 15 15
% 50504040
440 V
kA
>100 kA
50158866
% 10010050505050
500 V
kA 50106644
% 10010075757575
690 V
kA>100 kA33333333
% >100 kA 75 75 75 75 75 75 75 75
Associated fuses (if required)
if Isc > breaking capacity Icu
conforming to IEC 60947-2
230/240 V
aM
A
>100 kA
80 80
gL 100 100
400/415 V
aM
>100 kA
63 63 80 80
gL 80 80 100 100
440 V
aM
>100 kA
50 50 50 50 63 63
gL 63 63 63 63 80 80
500 V
aM 50 50 50 50 50 50
gL 63 63 63 63 63 63
690 V
aM >100 kA 16 25 32 32 40 40 40 40
gL >100 kA 20 32 40 40 50 50 50 50
Table 18: GV2P Breaking Capacity for European Applications
Type Units
Catalog Number Suffix (GV2P)
01–06 07 08 10 14 16 20 21 & 22 32
Rating
[1]
1
Ics = % of Icu.
A 0.1–1.6 2.5 4 6.3 10 14 18 23 & 25 32
Breaking capacity
conforming to IEC 60947-2
230/240 V
Ics
kA
>100 kA
%
400/415 V
kA
>100 kA
50 50 50
% 505050
440 V
kA
>100 kA
50 20 20 20
% 75757575
500 V
kA
>100 kA
50 42 10 10 10
% 100 75 75 75 75
690 V
kA>100 kA88666444
% >100 kA 100 100 100 100 100 100 100 100
Associated fuses (if required)
if Isc > breaking capacity Icu
conforming to IEC 60947-2
230/240 V
aM
A
>100 kA
gL
400/415 V
aM
>100 kA
100 100 100
gL 125 125 125
440 V
aM
>100 kA
50 63 80 80
gL 63 80 100 100
500 V
aM
>100 kA
50 50 50 50 50
gL 63 63 63 63 63
690 V
aM >100 kA 20 25 40 40 50 50 50 50
gL >100 kA 25 32 50 50 63 63 63 63