Brochure
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
13
6/2010
© 2001–2010 Schneider Electric
All Rights Reserved
Table 11: GV2AE Auxiliary Contact Specifications
Type Instantaneous Auxiliary Contacts GV2AE
Rated insulation voltage (Ui)
(associated insulation coordination)
Conforming to IEC 60947-1
250 V (690 V with respect to main circuit)
Conforming to CSA C22.2 No. 14 and
UL 508
300 V
Conventional rated thermal current (Ith)
Conforming to IEC 60947-5-1
2.5 A
Conforming to CSA C22.2 No. 14 and
UL 508
1 A
Operational power and current
AC operation
Conforming to IEC 60947-5-1
AC-15/100,000 close–open operations
Rated operational voltage (Ue) 24 V 48 V
110 V
127 V
230 V
240 V
Operational power,
normal conditions
48 VA 60 VA 120 VA 120 VA
Occasional breaking and making
capacities, abnormal conditions
480 VA 600 VA 1270 VA 2400 VA
Rated operational current (Ie) 2 A 1.25 A 1 A 0.5 A
Operational power and current
DC operation
Conforming to IEC 60947-5-1
DC-13/100,000 close–open operations
Rated operational voltage (Ue) 24 V 48 V 60 V —
Operational power,
normal conditions
24 W 15 W 9 W —
Occasional breaking and making
capacities, abnormal conditions
100 W 50 W 50 W —
Rated operational current (Ie) 1 A 0.3 A 0.15 A —
Low-level switching contact reliability Number of faults for n million operating cycles (17 V, 5 mA): = 10
-6
Short-circuit protection
GB2CB•• control circuit protector or control circuit fuse gG 10 A maximum
(or equivalent).
Wiring (screw clamp)
Number of conductors and wire size
Minimum Maximum
Solid cable 1 x 16–12 AWG (1–2.5 mm
2
) 2 x 16–12 AWG (1–2.5 mm
2
)
Flexible cable without cable end 1 x 18–12 AWG (0.75–2.5 mm
2
) 2 x 18–12 AWG (0.75–2.5 mm
2
)
Flexible cable with cable end 1 x 18–14 AWG (0.75–1.5 mm
2
) 2 x 18–14 AWG (0.75–1.5 mm
2
)
Wiring (spring terminal) Minimum (GVAN only) Maximum
Flexible cable without cable end 1 x 18–12 AWG (0.75–2.5 mm
2
) 2 x 18–12 AWG (0.75–2.5 mm
2
)
Tightening torque 12 lb-in (1.4 N•m) maximum
Contact operation
instantaneous auxiliary contacts
Contact Open
Contact Closed
Operation of fault
signaling contacts
GV2AM11
Change of state
following trip on
short circuit.
GV2AD10 and
AD01
Change of state
following trip on
short circuit,
overload or
undervoltage.
0 1
Power Pole
N.O.
N.O.
N.O.
N.C.
N.O.
N.C.
N.O.
N.O.
N.O.
N.C.
N.O.
N.C.
GVAN20
GVAN11
GVAE1
GVAE20
GVAE11
GVAD••10
GVAD••01