Brochure
© 2001–2010 Schneider Electric
All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors
Specifications and Operating Curves
12
6/2010
Table 10: GV Auxiliary and Fault Signaling Contact Specifications
Type Instantaneous Auxiliary Contacts
GVAN, GVAD
Fault Signaling Contacts
GV2AD, GV2AM11
Rated insulation voltage (Ui)
(associated insulation coordination)
Conforming to IEC 60947-1
690 V 690 V
Conforming to CSA C22.2 No. 14
and UL 508
600 V 300 V
Conventional rated thermal current
(Ith)
Conforming to IEC 60947-5-1
6 A 2.5 A
Conforming to CSA C22.2 No. 14
and UL 508
5 A 1 A
Operational power and current—
AC operation
Conforming to IEC 60947-5-1
AC-15/100,000 close–open operations AC-14/1000 close–open operations
Rated operational voltage (Ue) 48 V
110 V
127 V
230 V
240 V
380 V
415 V
440 V 500 V 690 V 24 V 48 V
110 V
127 V
230 V
240 V
Operational power,
normal conditions
300 VA 500 VA 720 VA 850 VA 650 VA 500 VA 400 VA 36 VA 48 VA 72 VA 72 VA
Occasional breaking and making
capacities, abnormal conditions
3000 VA 7000 VA 13,000 VA 15,000 VA 13,000 VA 12,000 VA 9000 VA 220 VA 300 VA 450 VA 450 VA
Rated operational current (Ie) 6 A 4.5 A 3.3 A 2.2 A 1.5 A 1 A 0.6 A 1.5 A 1 A 0.5 A 0.3 A
Operational power and current—
DC operation
Conforming to IEC 60947-5-1
DC-13/100,000 close–open operations DC-13/1000 close–open operations
Rated operational voltage (Ue) 24 V 48 V 60 V 110 V 240 V
[1]
1
Add an RC circuit, Type LA4D, to the load terminals. Consult the Digest.
— — 24 V 48 V 60 V —
Operational power,
normal conditions
140 W 240 W 180 W 140 W 120 W — — 24 W 15 W 9 W —
Occasional breaking and making
capacities, abnormal conditions
240 W 360 W 240 W 210 W 180 W — — 100 W 50 W 50 W —
Rated operational current (Ie) 6 A 5 A 3 A 1.3 A 0.5 A — — 1 A 0.3 A 0.15 A —
Low-level switching contact
reliability
Number of faults for n million operating cycles (17 V, 5 mA): = 10
-6
Short-circuit protection GB2CB•• control circuit protector or control circuit fuse gG 10 A maximum (or equivalent).
Wiring (screw clamp)
Number of conductors and
wire size
Minimum Maximum
Solid cable 1 x 16–12 AWG (1–2.5 mm
2
) 2 x 16–12 AWG (1–2.5 mm
2
)
Flexible cable without cable end 1 x 18–12 AWG (0.75–2.5 mm
2
) 2 x 18–12 AWG (0.75–2.5 mm
2
)
Flexible cable with cable end 1 x 18–14 AWG (0.75–1.5 mm
2
) 2 x 18–14 AWG (0.75–1.5 mm
2
)
Wiring (spring terminal) Minimum (GVAN only) Maximum (GVAN only)
Flexible cable without cable end 1 x 18–12 AWG (0.75–2.5 mm
2
) 2 x 18–12 AWG (0.75–2.5 mm
2
)
Tightening torque 12 lb-in (1.4 N•m) maximum