Table 8: Technical Characteristics
Type GV2ME GV2P LS1D30,
LS1D303
LS1D32,
LS1D323
[1]
Utilization category
Conforming to IEC 60947-2 A A
—AC 20B#
Conforming to IEC 60947-4-1 AC-3 AC-3
Rated operational voltage (Ue)
Conforming to IEC 60947-2 690 V 690 V 690 V 690 V
Rated insulation voltage (Ui)
Conforming to IEC 60947-2 690 V 690 V
— 690 V
Conforming to
CSA C22.2 No. 14 and UL 508
600 V 600 V
Rated operational frequency
Conforming to IEC 60947-2 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse withstand voltage (U imp)
Conforming to IEC 60947-2 6 kV 6 kV — —
Total power dissipated per pole (W)
2.5 W 2.5 W 3.2 W 3.2 W
Mechanical life (close-open operations)
(varies with conditions)
100,000 — — —
Electrical life (close-open operations)
(for AC-3 duty)
100,000 100,000 — —
Duty class (close-open operations/hr)
(maximum operating rate)
25 25 — —
Rated duty
Conforming to IEC 60947-4-1 —
Continuous
duty
——
1
Conforming to IEC 60947-3
Table 9: GV2 Trip Module Specifications
Type GV2AU GV2AS
Rated insulation voltage (Ui)
Conforming to IEC 60947-1 690 V 690 V
Operational voltage (Ue)
Conforming to IEC 60947-1 0.85-1.1 V 0.7-1.1 V
Drop-out voltage (Ue)
0.35-0.7 V 0.2-0.75 V
Inrush consumption
12 VA 14 VA
8 W 10.5 W
Sealed consumption
3.5 VA 5 VA
1.1 W 1.6 W
Operating time (ms)
Conforming to IEC 60947-1
From the moment the voltage reaches its operational value until
opening of the GV2•• 10–15 ms
On-load factor
100%
Wiring Minimum Maximum
Number of conductors and wire size
Solid cable 1 x 16–12 AWG (1-2.5 mm
2
) 2 x 16–12 AWG (1–2.5 mm
2
)
Flexible cable without cable end 1 x 18–12 AWG (0.75-2.5 mm
2
) 2 x 18–12 AWG (0.75–2.5 mm
2
)
Flexible cable with cable end 1 x 18–14 AWG (0.75-1.5 mm
2
) 2 x 18–14 AWG (0.75–1.5 mm
2
)
Tightening torque
12 lb-in (1.4 N•m) maximum