GV2 Specifications
Table 7: Environment
Type GV2ME GV2P LS1D30,
LS1D303
LS1D32,
LS1D323
Conforming to standards
IEC 60947-1, 60947-2, 60947-4-1, EN 60204, BS 4752, BS 4941, UL 508, CSA C22.2 No. 14, NF C 63-650,
NFC63-120, 79-130, VDE 0113, 0660.
Product approvals
DEMKO, NEMKO, SEMKO, CSA. UL,
BV, GL, LROS, DNV, PTB
CSA, UL, PTB UL, CSA BV
UL File Number
File E164864, CCN NLRV
File E197164
CCN IZLT
File E197164
CCN IZLT2
CSA File Number
File LR 81630, Class 3211 05 File 222370, Class 6225-01
Protective treatment
“TH” “TH”
Degree of protection
Conforming to IEC 60529
GV2ME01 enclosure: IP41
GV2ME02 enclosure: IP55
——
Shock resistance
Conforming to IEC 60068-2-27
30 g 30 g
Vibration resistance
Conforming to IEC 60068-2-6
5 to 150 Hz (5 g) 5 to 150 Hz (5 g)
Ambient air temperature
Storage
-40 to +176 °F (-40 to +80 °C) -40 to +176 °F (-40 to +80 °C)
Operation
Open: -4 to +140 °F (-20 to +60 °C)
Enclosed: -4 to 104 °F (-20 to 40 °C)
-4 to +140 °F (-20 to +60 °C)
-58 to +158 °F
(-50 to +70 °C)
-58 to +158 °F
(-50 to +70 °C)
Temperature compensation
Open: -4 to +140 °F (-20 to +60 °C)
Enclosed: -4 to 104 °F (-20 to 40 °C)
-4 to +140 °F (-20 to +60 °C)
Flame resistance
Conforming to IEC 60695-2-1
1760 °F (960 °C)
Maximum operating altitude
6562 ft (2000 m) 6562 ft (2000 m)
Operating positions in
relation to the normal
vertical mounting position
± 23 °
Wiring
Number of conductors and
wire size
Maximum Minimum Maximum Minimum Maximum Minimum
Solid cable
2 x 8 AWG
(2 x 6 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
2 x 8 AWG
(2 x 6 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
2 x 8 AWG
(2 x 6 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
Flexible cable
without cable end
2 x 8 AWG
(2 x 6 mm
2
)
2 x 14 AWG
(2 x 1 mm
2
)
2 x 8 AWG
(2 x 6 mm
2
)
2 x 14 AWG
(2 x 1 mm
2
)
2 x 8 AWG
(2 x 6 mm
2
)
2 x 14 AWG
(2 x 1 mm
2
)
Flexible cable
with cable end
2 x 10 AWG
(2 x 4 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
2 x 10 AWG
(2 x 4 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
2 x 10 AWG
(2 x 4 mm
2
)
2 x 16 AWG
(2 x 1 mm
2
)
Suitable for isolation
Conforming to IEC 60947-1 /
60947-1-6
Yes Yes
Tightening torque
15 lb-in (1.7 N•m)
Resistance to mechanical
impact
0.5 J 0.5 J
Sensitivity to phase failure
Conforming to IEC 60947-4-1, paragraph 7-2-1-5-2
90°
90°
90°
90°
90°
90°
30°
30°