GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Catalog 2520CT0001R04/09 2010 Class 2520
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Table of Contents Table of Contents INTRODUCTION ......................................................................................... 5 STANDARD FEATURES ............................................................................. 5 SHORT-CIRCUIT CURRENT RATINGS ..................................................... 7 UL 508 Type E ......................................................................................
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors 4 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection and control.1 The GV2 and GV3 manual starters and protectors provide manual isolation, manual motor control, and overcurrent protection in one compact unit.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Table 1: Standard Features GV2ME GV2P 0.1 to 32 A Up to 20 hp @ 460 V 10 kA SCCR @ 480 V Push Button Operator 0.1 to 30 A Up to 15 hp @ 460 V 50 kA SCCR @ 480 V Rotary Handle Operator Visible Trip Indication Protection Thermal-magnetic (overload relays are bimetallic—Class 10) Mounting • • Clip-on mounting on 35 mm DIN rail. Unclips without the use of a tool. Panel mounts using a metal adapter plate.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Short-Circuit Current Ratings Short-Circuit Current Ratings UL 508 Type E Table 2: Manual Self-Protected Combination Motor Controller, TeSys® GV Manual Self-Protected Combination Starter Meeting UL 508 Type E, UL File E164871 TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars (multiple starters) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 120 V 240 V
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Short-Circuit Current Ratings UL 508 Type F Table 4: Combination Motor Controller, TeSys® GV Manual Self-Protected Combination Starter Meeting UL 508 Type F, UL File E164871 TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars (multiple starters) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 120 V Associated Cable, AWG 75 °C, Cu Type of Manual Overload T
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Short-Circuit Current Ratings UL 508 Group Motor Installations Table 6: TeSys GV2ME Horsepower and SCCR Ratings In association with LC1D contactors, suitable for group installation when protected by fuses or an inverse-time circuit breaker (when used with GV1G09 terminal or GV2G05 blocks plus GV2G busbars) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 120 V 240 V Manual Combination Motor Controller, TeSys® GV GV2ME: UL File E164864 (MC 1
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Specifications and Operating Curves GV2 Specifications Table 7: Environment Type GV2ME GV2P LS1D30, LS1D303 Conforming to standards IEC 60947-1, 60947-2, 60947-4-1, EN 60204, BS 4752, BS 4941, UL 508, CSA C22.2 No. 14, NF C 63-650, NFC63-120, 79-130, VDE 0113, 0660. Product approvals DEMKO, NEMKO, SEMKO, CSA.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 8: Technical Characteristics Type GV2ME Utilization category Rated operational voltage (Ue) GV2P Conforming to IEC 60947-2 A A Conforming to IEC 60947-4-1 AC-3 AC-3 Conforming to IEC 60947-2 690 V 690 V LS1D30, LS1D303 LS1D32, LS1D323 [1] — AC 20B# 690 V 690 V — 690 V Conforming to IEC 60947-2 690 V 690 V Rated insulation voltage (Ui) Conforming to CSA C22.2 No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 10: GV Auxiliary and Fault Signaling Contact Specifications Type Instantaneous Auxiliary Contacts GVAN, GVAD Fault Signaling Contacts GV2AD, GV2AM11 Rated insulation voltage (Ui) (associated insulation coordination) 690 V Conforming to IEC 60947-1 Conforming to CSA C22.2 No. 14 and UL 508 Conventional rated thermal current (Ith) 690 V 600 V 300 V 6A 2.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 11: GV2AE Auxiliary Contact Specifications Type Instantaneous Auxiliary Contacts GV2AE Rated insulation voltage (Ui) (associated insulation coordination) 250 V (690 V with respect to main circuit) Conforming to IEC 60947-1 Conforming to CSA C22.2 No. 14 and UL 508 Conventional rated thermal current (Ith) Conforming to IEC 60947-5-1 Conforming to CSA C22.2 No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 12: GV2 Accessory Specifications 3-Pole Busbars GV2G• Rated insulation voltage (Ui) Conforming to IEC 60947-1 690 V Conventional rated thermal current (Ith) Conforming to IEC 60439-1 63 A Permissible peak current (I peak) 11 kA Permissible thermal limit (I2t) 104 kA2s Degree of protection Conforming to IEC 60529 IP20 Terminal Blocks GV2G05 and GV1G09 Rated insulation voltage (Ui) Co
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV2 Operating Curves Table 13: Thermal-Magnetic Trip Curves for GV2ME and GV2P Average operating time at 68 °F (20 °C) as a function of multiples of the setting current Time (s) 10,000 1000 100 1 10 2 3 1 0.1 0.01 0.001 1 1.5 10 100 x setting current (lr) 1. 3 poles from cold state 2. 2 poles from cold state 3.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 14: Current Limitation on Short Circuit For GV2M and GV2P 3Ø, 400/415 V Dynamic stress 1 peak = f (prospective Isc) at 1.05 Ue = 435 V Maximum peak current (A) 100,000 = 0. 3 = 0.2 5 1 2 0. 5 3 = 4 10,000 8 = 0. 7 5 = 0. 6 = 0. 9 7 co sϕ = 0. 95 8 9 1000 10 100 100 1000 10,000 15,000 (11) 100,000 Prospective Isc (A) 1. I peak maximum 7. 4–6.3 A 2.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 15: Thermal Limit on Short Circuit for GV2ME Thermal limit in kA2s in the magnetic operating zone Sum of l2dt = f (prospective Isc) at 1.05 Ue = 435 V 2 2 Sum of I dt (kA s) 100 2 3 4 5 1 6 7 10 8 9 1 10 0.1 0.01 0.1 1 10 100 Prospective Isc (kA) 1. 24–32 A 6. 6–10 A 2. 20–25 A 7. 4–6.3 A 3. 17–23 A 8. 2.5–4 A 4. 13–18 A 5.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 16: Thermal Limit on Short Circuit for GV2P Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V 2 2 Sum of I dt (kA s) 100 1 2 3 4 5 6 10 7 8 1 9 0.1 0.01 0.1 1 10 1. 24–32 A 6. 6–10 A 2. 20–25 A 7. 4–6.3 A 3. 17–23 A 8. 2.5–4 A 4. 13–18 A 5. 9–14 A 100 Prospective Isc (kA) 9. 1.6–2.5 A 10. 1–1.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 17: GV2ME Breaking Capacity for European Applications Type Rating [1] A conforming to IEC 60947-2 440 V Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2 440 V 500 V 690 V 14 16 20 21 22 0.1–1.6 2.5 4 6.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 19: GV2P•• Breaking Capacity for European Applications When Used with Current Limiter GV1L3 Type Rating [1] A Breaking capacity conforming to IEC 60947-2 07 08 10 14 16 20 21 & 25 32 0.1–1.6 2.5 4 6.3 10 14 18 21 & 23 32 % >100 kA kA 400/415 V Ics 440 V % kA 100 >100 kA % kA 500 V 50 100 >100 kA % 50 Ics = % of Icu.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV3 Specifications Table 21: Environment Conforming to standards IEC, NF C, BS, IEC, VDE Approvals ASE, CSA, UL, LROS, ÖVE UL File Number File E164864, CCN NLRV CSA File Number File LR 81630, Class 3211 05 Protective treatment “TC” Degree of protection Conforming to IEC 60529 Open GV3P: IP20 Shock resistance Conforming to IEC 68-2-27 On: 15 gn - 11 ms Off: 30 gn - 11 ms Vibration resis
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 24: Characteristics of Electrical Trip Units Manual Starter and Protector Type GV2ME, GV2P, and GV3P Catalog number suffix GV2ME only [1] GV7R GV7AU GVAS GVAX 690 V 690 V 500 V 690 V 690 V 600 V 600 V — 600 V 600 V 0.7–1.1 V 0.85–1.1 V 0.85–1.1 V 0.7–1.1 V 0.2–0.75 Ue Rated insulation voltage (Ui) Operational voltage (Un) Conforming to IEC 60947-1 0.85–1.1 V 0.7–0.35 Un 0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV3 Auxiliary Contact Specifications Table 25: Auxiliary Contacts for GV2 and GV3P Manual Motor Starters, Controllers, and Protectors Type of contacts Units Instantaneous auxiliary GVAN, GVAD Fault signaling GVAD, GVAM11 Instantaneous auxiliary GVAE Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 690 250 (690 in relation to main circuit) (associated insulation coordination) C
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV3 Operating Curves Table 26: Thermal-Magnetic Trip Curves for GV3P Average operating times at 68 °F (20 °C) related to multiples of the setting current NOTE: GV3ME is not available in the USA. Time (s) 10,000 1000 100 10 1 0.1 0.01 0.001 1 10 100 x the setting current (Ir) 1a. 3 poles from cold state (lr minimum): GV3 P 1b. 3 poles from cold state (lr maximum): GV3 P 2a.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 27: Current Limitation on Short Circuit for GV3P Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V NOTE: GV3ME is not available in the USA. Limited peak current (kA) 100 10 1 1 10 15 100 Prospective Isc (kA) 1. Maximum peak current 6. 23–32 A 2. 56–80 A 7. 17–25 A 3. 48–65 A 8. 12–18 A 4. 37–50 A 9. 9–13 A 5.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 28: Thermal Limit on Short Circuit for GV3P Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V GV3ME is not available in the USA. 2 2 Sum of I dt (kA s) 1000 100 10 1 1 10 15 100 Prospective Isc (kA) 1. 56–80 A (GV3 ME80) 5. 23–32 A (GV3 P32) 2. 48–65 A (GV3 P65) 6. 17–25 A (GV3 P25) 3. 37–50 A (GV3 P50) 7.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV7 Specifications Table 29: Environment Conforming to standards IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, 60947-4-1, NF C 63-650, 63-120, 79-130, VDE 0113, UL 508, CSA C22.2 No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 31: Technical Characteristics GV7 Type RE20–RE100 RS40–RS100 RE150 RS150 RE220 RS220 Conforming to IEC 60947-2 A A A Conforming to IEC 60947-4-1 AC-3 AC-3 AC-3 Rated operational voltage (Ue) conforming to IEC 60947-2 690 V 690 V 690 V Rated insulation voltage (Ui) conforming to IEC 60947-2 750 V 750 V 750 V Rated voltage conforming to CSA C22.2 No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV7 Auxiliary Contact Specifications Table 33: Auxiliary Contact Characteristics Type of contacts Rated insulation voltage (Ui) (associated insulation coordination) Conventional thermal current (Ith) Conforming to IEC 60947-1 from CSA C22.2 No. 14 and UL 508 V Conforming to IEC 60947-5-1 from A CSA C22.2 No. 14 and UL 508 Mechanical durability GV7AE11 GV7AB11 690 690 6 6 C.O. 50 000 (C.O.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves GV7 Operating Curves The current limiting capacity of the motor starter and protector is expressed by two curves that illustrate the following, as a function of the prospective short-circuit current (the current that would flow if no protection devices were installed): • • The actual peak current (limited) The thermal stress (in A2s), that is, the energy dissipated by the short-circuit in a conductor
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 36: Thermal-Magnetic Trip Curves for GV7R Average operating time at 68 ºF (20 ºC) as a function of multiples of the setting current Time (s) 10,000 5000 2000 1000 500 200 100 50 20 10 5 1 2 2 1 0.5 3 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 1 1.12 2 3 4 5 7 10 20 30 40 50 70 100 x setting current (lr) 1. Curve from cold state 2. Curve from hot state 3.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 37: Current Limitation on Short Circuit for GV7R 3Ø, 400/415 V Dynamic stress 1 peak = f (Prospective Isc) 100 For GV7RE only 80 70 60 50 Limited peak current (kA) 1. GV7RE220 2. GV7RE150 3.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 39: Thermal Limit on Short Circuit for GV7R 3Ø, 400/415 V 10 7 Thermal limit I2dt = f (Prospective Isc) 5 x 10 6 For GV7RE only Sum of i2dt (A2s) 3 x 10 6 2 x 10 1. GV7RE220 2. GV7RE150 3.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 41: Current Limitation on Short Circuit for GV7R 3Ø, 690 V 50 Dynamic stress 1 peak = f (Prospective Isc) 40 For GV7RE only Limited peak current (kA) 30 1. GV7RE220 2. GV7RE150 and GV7RE100 20 1 2 10 8 7 6 5 4 2 3 4 5 6 9 10 20 Prospective short-circuit current, Isc (kA) Table 42: Current Limitation on Short Circuit for GV7RS For GV7RS only 50 Limited peak current (kA) 1.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves Table 43: Thermal Limit on Short Circuit for GV7R 3Ø, 690 V 3 x 10 6 2 x 10 6 Thermal limit I2dt = f (Prospective Isc) For GV7RE only Sum of I2dt (A2s) 1. GV7RE220 2.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Specifications and Operating Curves 36 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Selection Disconnect Fuse or Circuit Breaker Motor TeSys D or TeSys K Contactor GV2 Manual Motor Starter Example 1: Fuse and Circuit Breaker Selection When selecting the proper upstream short circuit protection for Group Motor installations, you must apply the specific rules of the National Electrical Code (NEC) for Group Motor installations.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection GV2 and GV3 Selection Table 47: GV2 Manual Motor Controller and Protector Horsepower Ratings Catalog Number Push Button GV2ME Rotary Handle [1] GV2P Thermal Trip Setting Range (A) Maximum Horsepower Ratings 1Ø 120 V 208 V 3Ø 240 V 208 V 240 V 480 V 600 V GV2ME01 GV2P01 0.11–0.16 — — — — — — — GV2ME02 GV2P02 0.016–0.25 — — — — — — — GV2ME03 GV2P03 0.25–0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection GV7 Selection Standard manual controllers and protectors include terminal and device mounting hardware. Cable clamps and accessories are listed on page 49. Table 49: GV7R•••• Manual Motor Controller and Protector Horsepower Ratings Thermal Trip Setting Range (A) 460 V 5 10 15 GV7RE20 15–25 7.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection GV2 and GV3 Accessories Figure 1: GV2 Accessories GV2V02•• GV1L3 GV2AK00 GV2ME GVAD•• GVAM11 GVAU GV2P GVAM11 GVAS GVAE11, AE20 LS1D30 GVAE1 (N.C.) GVAN•• Table 50: GVAN•• GVAE1 (N.O.) Flip the window cover 180° GV2 and GV3 Auxiliary Contact Blocks Description Instantaneous auxiliary contacts Mounting Location Max. No. of Blocks Contact Type Sold in Lots of Catalog Number Weight lb (kg) Front [1] 1 N.O.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Figure 2: GV3 Accessories GV3G364 GV3G264 GVAU•• GVAD•• GVAM11 GV3P GVAS•• GVAM11 GVAE113, GVAE203, GVAED1013, GVAED0113 GVAE11, GVAE20, GVAED101, GVAED011 GVAN•• GVAN•• GVAE Flip the window cover 180° to change from N.O. to N.C. or vice versa. GVAE1 GV2V03 Table 51: GV3 Auxiliary Contact Blocks Description Mounting Location Front [1] Max. No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Table 52: Electrical Trip Units Description Voltage Hz Catalog No.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Table 55: Accessories for GV3P Description 3-pole, 115 A busbars Pitch 64 mm GV3G66 For Manual Motor Controllers Catalog Number Weight lb (kg) 2 tap-off GV3P•• GV3G264 [1] 0.33 (0.15) 3 tap-off GV3P•• GV3G364 [1] 0.55 (0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Figure 3: GV2 Accessories GV2G454 GV2G254 LAD31 GV1G09 GV2G454 LAD31 GV2G254 GV1G10 GV2G05 LA9E07 GV2AF01 GV2AF4 GV2AF3 LAD311 GK2AF01 GV2AF02 GV1G02 GV2AP02 .
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Table 56: GV2 Accessories Busbars Description No. of GV Starters 2 GV2GH7 Sets of 3-pole, 63 A busbars 3 4 5 No. of Side-Mounted Auxiliary Blocks on Each GV Starter Busbar Pitch (mm) Sold in Lots of Catalog Number Weight, lb (kg) none 45 1 GV2G245 0.08 (0.036) 1 GV2AN, AM, AD 54 1 GV2G254 0.084 (0.038) 1 or 2 GV2AN, AM, AD; or 1 GV2AS, AU 72 1 GV2G272 0.09 (0.042) None 45 1 GV2G345 0.12 (0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Figure 4: GV2M Enclosures GV2V01 GV2MC• GV2K• GV2MP•• GV2SN• GV2E01• 46 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Table 57: GV2ME Enclosures Application Type For GV2ME manual starters and protectors, with or without accessories Surface mounting, double insulated with protective (sealable) cover GV2MC, GV2MP01, and GV2MP02: Maximum of 1 accessory on the right and 1 on the left GV2MP03 and GV2MP04: Flush, with protective cover 1 accessory on the right only Table 58: Degree of Protection of Enclosure Weight, lb (kg) 0.64 (0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection 48 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection GV7 Accessories Standard manual controllers and protectors include terminal- and device-mounting hardware. Select cable clamps and accessories from Table 59. GV7AC03 GV7AC01 GV7AC02 GV7AC04 GV7RE, RS GV7AC01 GV7AC04 Table 59: I Cabling Accessories Description Box lugs Application Sold in Lots of For Contactor Catalog Number Weight, lb (kg) GV7R•40 through GV7R•150: 14–3/0 AWG (1.5–95 mm2) 3 — GV7AC021 0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Auxiliary Contacts Auxiliary contacts remotely indicate the state of the contacts in the starter. The auxiliary contacts can be used for signaling, electrical locking, or relaying. Standard and low-level versions are available. The auxiliary contacts include a terminal block. A hole is provided for wiring exit.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Magnetic Fault Indicators The magnetic fault indicator does one of the following: • • differentiates a thermal fault from a magnetic fault opens the contactor only in the event of a thermal fault (see page 50) Table 62: Magnetic Fault Indicators Voltage Catalog Number 24–48 Vac / 24–72 Vdc GV7AD111 110–240 Vac/Vdc GV7AD112 Weight, lb (kg) 0.22 (0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Figure 6: GV7R Starter with Options and Accessories GV7AP03 Direct rotary handle ON GV7RE, RS Starter O OFF ON ON O OFF GV7AP04 Direct rotary handle O OFF ON GV7AP05 Conversion accessory O OFF GV7AP01, AP02 Extended rotary handle ON O OFF ON GV7V01 Locking device O OFF 52 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection Direct Rotary Handle The direct rotary handle accessory replaces the front cover of the starter and is secured by screws. Refer to Figure 6 on page 52. The handle includes a device for padlocking the starter in the Off (O) position. As many as three padlocks with a shank diameter of 5–8 mm (0.2–0.3 in.) can be used. The padlocks are not supplied.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams Mounting Dimensions and Wiring Diagrams GV2 Mounting Dimensions LS1D7323: 3.92 101 = .59 15 1.8 45 .39 10 = X1 X1 3.5 89 ··· 1.8 44.5 X1 .37 9.3 .37 9.3 3.2 81(1) 63 16 .71 18 46 1.8 44.5 X1 3.92 101 = = GV2ME··3: 1.7 44 2.6 66 LS1D30 Block GV2AD, AM, AN Block GV2AU, AS .43 .63 11 16 GV2AE 1.8 45 GV2AD, AM AN, AU, AS, AX 3.5 89 GV2ME 67.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams Mounting of GV2P On Pre-Slotted Mounting Plate, AM1PA On Adapter Plate, GK2AF01 35 1.38 1.8 45 3.3 84 1.8 44.5 .53 13.5 C Ø5.5 .22 45 1.77 5.3 135 3.3 84 2.2 55 1.8 44.5 35 1.38 AF1EA4 5 .2 On Panel .94 24 .53 13.5 .37 9.5 105 ±5 4.13 ±.2 On 35 mm (1.4 in.) Rail 54 2.13 C = 3.09 in. (78.5 mm) on AM1DP200 (35 x 7.5 mm) C = 3.39 in.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams ( Mounting of External Operator GV2AP01 or GV2AP02 Door Cut-out 2.1 54 = 1.7 43 = 2.6 65 .28 7 4x0.14 4x3.5 2.1 53 .06-20 1.5-5 .20 .24 5.2 6 = = (1) = = 2.1 54 1. 135 mm minimum, 284 mm maximum with operating rod uncut, 88 with operating rod cut. Surface Mounting Enclosure GV2MC0• = 2x0.21x0.25 (1) 2x5.3x6.3 .83 21 2.4 62 4.6 118 5.2 133 = = 5.1 130 5.8 147 = 2x0.13 2x3.3 0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams Sets of Busbars GV2G445, GV2G454, and GV2G472 with Terminal Block GV2G05 a l p 2.5 63 .71 18 .12 3 1.8 45 l p GV2G454 0.16 x 2.1 in. (4 x 54 mm) 8.1 in. (206 mm) 2.1 in. (54 mm) GV2G445 0.16 x 1.8 in. (4 x 45 mm) 7.0 in. (179 mm) 1.8 in. (45 mm) GV2G472 0.16 x 2.8 in. (4 x 72 mm) 10.2 in. (260 mm) 2.8 in. (72 mm) a No. of Taps 5 6 7 8 GV2G454 10.2 in. (260 mm) 12.4 in.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams GV3 Mounting Dimensions Dimensions 3.94 100 2.52 64 5.73 145.5 5.2 132 2.68 68 GV3G66 Shroud 1.89 47.9 2.5 63.55 (2) 0.45 11.4 X1 (1) X1 5.35 136 0.71 18 0.35 9 2.17 55 X1 = Electrical clearance (ISC max) 40 mm for Ue < 500 V, 50 mm for Ue < 690 V 1. Blocks GVAN••, GVAD•• and GVAM11 2.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams GV7 Mounting Dimensions Motor Controllers GV7R Motor Controllers with Terminal Shields and Phase Barriers GV7R + GV7AC01 + GV7AC04 (2) (3) 4.13 105 4.37 86 111 (1) = 14.06 357 = = = = 3.19 81 3.39 = = 12.64 321 6.34 = 161 = = = 4.92 125 6.34 161 = = = = = = = 1.38 35 3.19 81 1. 126 for GV7R• 220 2. Phase barriers—GV7AC04 3. Terminal shields—GV7AC01 x1 x2 in. (mm) in.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams On Panel On Two DZ5MB201 Mounting Rails 2xØ0.24 2xØ6 4.92 125 = 5.31 135 4.92 125 = DZ5-ME5 1.38 1.38 1.38 35 35 35 1.38 35 0.59 15 Flush Mounting 4.25 108 = = 4.25 108 = Controllers GV7R Side by Side = 1.85 3.0 47 76 1 Starter GV7R 1.14 29 3.46 88 3.27 83 == 1.14 29 = = 4.25 108 Combination of GV7R and LC1F with Kit GV7AC0• in. (mm) Ø0.28x0.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams Spreaders GV7AC03 4.49 114 Smooth Terminals 1.77 45 Connectors Z 1.61 41 1.77 45 Cabling a Z Z 2.76 70 2.76 70 X 0.75 19 0.41 10.5 1.18 30 X X a 0.85 in. (21.5 mm) 0 1.85 3.0 47 76 1.77 DD 60 GV7R•220 Flush Mounting I 60 0.77 in. (19.5 mm) 2.87 45 73 Direct Rotary Handle GV7AP03, GV7AP04 GV7R• 1.10 28 6.10 155 4.76 121 3.58 91 1.14 29 2.17 1.42 55 36 3.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams GV2 Wiring Diagrams 5/L3 5/L3 3/L2 3/L2 6/T3 1/L1 1/L1 5/L3 4/T2 3/L2 6/T3 Current Limiter GV1L3 2/T1 1/L1 4/T2 GV2P 2/T1 GV2ME Front Mounting Add-on Contact Blocks Instantaneous Auxiliary Contacts GVAE1 GVAE11 GVAE20 13 23 24 21 22 14 13 11 12 14 13 14 or Side Mounting Add-on Contact Blocks Instantaneous Auxiliary Contact and Fault Signaling Contacts 97 51 52 53 54
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams Use of Fault Signaling Contact and Short-Circuit Signaling Contact GVAM1 GVAD10 Short-circuit signaling N.C. or N.O.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Mounting Dimensions and Wiring Diagrams GV7 Wiring Diagrams 21 24 22 84 82 94 92 91 81 14 12 5/L3 3/L2 Add-on Auxiliary Contacts GV7AE11, GV7AB11 A self-adhesive label, supplied with the contact, can be affixed to the front face of the starter to allow personalized marking as a function of the contact or contacts.
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors © 2001–2010 Schneider Electric All Rights Reserved 65 6/2010
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors 66 6/2010 © 2001–2010 Schneider Electric All Rights Reserved
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors © 2001–2010 Schneider Electric All Rights Reserved 67 6/2010
Schneider Electric USA, Inc. 8001 Knightdale Blvd. Knightdale, NC 27545 1-888-Square D 1-888-778-2733 www.schneider-electric.