Product Overview
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jun 29, 2014
1
Product data sheet
Characteristics
GV2ME22
TeSys GV2-Circuit breaker-thermal-magnetic -
20...25 A - screw clamp terminals
Main
Range TeSys
Product name TeSys GV2
Device short name GV2ME
Product or component
type
Circuit breaker
Circuit breaker applica-
tion
Motor protection
Poles description 3P
Network type AC
Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity Icu = 4 kA at 500 V AC 50/60 Hz conforming to IEC
60947-2
Icu = 6 kA at 440 V AC 50/60 Hz conforming to IEC
60947-2
Icu = 15 kA at 400/415 V AC 50/60 Hz conforming to
IEC 60947-2
Icu = 3 kA at 690 V AC 50/60 Hz conforming to IEC
60947-2
Icu = 50 kA at 230/240 V AC 50/60 Hz conforming to
IEC 60947-2
[Ics] rated service
short-circuit breaking
capacity
40 % at 400/415 V AC 50/60 Hz conforming to IEC
60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC
60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC
60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC
60947-2
Thermal protection ad-
justment range
20...25 A
Trip unit technology Thermal-magnetic
Magnetic tripping cur-
rent
327 A
Complementary
Mounting mode By clips
By screws
Mounting support Rail
Mounting position Horizontal
Vertical
Motor power kW 15 kW at 500 V AC 50/60 Hz
11 kW at 400/415 V AC 50/60 Hz
Control type Pushbutton
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 25 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles