Product Overview

Table Of Contents
31
Altistart 22 soft start/soft stop units for 3-phase power supply voltage 208...600 V and 110 V control
power supply—Connection in the motor power supply line
Motor power
in HP
208 V 3 7.5 15 20 25 30 40
230 V 5 10 15 20 25 30 40 50
460 V 10 10 30 40 50 60 75 100
575 V 15 25 40 50 60 75 100 125
Nominal current IcL (A) (1)
17 32 47 62 75 88 110 140
Number of
starts/hour
Without fan 6 6 6 6 6 6 4 4
With fan (2) 10 10 10 10 10 10 10 10
Dimensions:
W x D x H
(mm)
130 x 265 x 169 145 x 295 x 207 150 x 356 x 229
Reference
ATS22D17S6U ATS22D32S6U ATS22D47S6U ATS22D62S6U ATS22D75S6U ATS22D88S6U ATS22C11S6U ATS22C14S6U
Note: All values given for Altistart 22 starters are dened for 3.5 x In and 20s starting time, with motors with thermal protection class 10. These values are for an ambient temperature of 40 °C.
(1) IcL corresponds to the starter rating. (2)
All soft starters from motor power 75 HP to 200 HP (ATS22C21.. to ATS22C59..) are equipped with a fan as standard.
Altistart™ 01 soft starters for 0.37 to 15 kW / 0.5 to 20 HP motors
Altistart 22 soft starters for 3 to 500 HP motors
Altistart™ 01 soft starters for 0.37 to 11 kW motors and single or 3-phase supply voltage
110...480 V 50/60 Hz (1)
Power for single-phase motor (2)
Under 230 V (kW) 0.37 0.75 1.1 1.5
Power for 3-phase motor (2)
Under 110 V (HP) 0.5 1 1.5
Under 230 V (kW) 0.37 0.55 0.75 1.1 1.5 2.2
Under 230 V (HP) 0.5 1 1.5 2 3
Under 400 V (KW) 1.1 2.2 3 4 5.5
Under 460 V (HP) 0.5 1.5 2 3 5 7.5
Nominal current IcL (A) (3)
3 6 9 12
Dimensions: W x D x H (mm)
22.5 x 100.4 x 100 45 x 130.7 x 124
Reference ATS01N103FT ATS01N106FT ATS01N109FT ATS01N112FT
Altistart 01 soft start/soft stop units for 0.75 to 15 kW motors (4) and 3-phase supply voltage
220...240 V 50/60 Hz (5)
Power for 3-phase motor 220...240 V 50/60 Hz (kW) (2)
0.75/1.1 4/5.5 7.5
Power in HP (2)
1/1.5 5/7.5 10
Nominal current IcL (A) (3)
6 22 32
Dimensions: W x D x H (mm)
45 x 130.7 x 124 45 x 130.7 x 154
Reference ATS01N206LU ATS01N222LU ATS01N232LU
Altistart 01 start/soft stop units for 0.75 to 15 kW motors (4) and 3-phase supply voltage
440...480 V 50/60 Hz (5)
Power for 3-phase motor 440...480 V 50/60 Hz (kW) (2)
Power in HP (2)
2/3 5 7.5 10/15 20
Nominal current IcL (A) (3)
6 9 12 22 32
Dimensions: W x D x H (mm)
45 x 130.7 x 124 45 x 130.7 x 154
Reference ATS01N206RT ATS01N209RT ATS01N212RT ATS01N222RT ATS01N232RT
(1) Number of possible start-stops/hour: 100 for starting time of 1 s maximum, 20 for starting time of 5 s maximum.
(2) Standard motor power ratings, HP power ratings indicated according to standard UL508. (3) IcL corresponds to the starter rating. (4) Control power supply built into the starter.
(5) Number of possible start-stops/hour: 100 for starting time of 1 s maximum, 20 for starting time of 5 s maximum, 10 for starting time of 10 s maximum.