Product Overview
Table Of Contents
23
Consult the Schneider Electric Digest for more product selection options and information.
NEMA and denite purpose motor control
Circuit breaker + contactor + overload relay
Motor HP 460 V 1/2 3/4 1 1-1/2 2 3 5 7-1/2
Full load current
(NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A
Circuit breaker (1)
BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36025
Interrupting rating 480 V 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA
Ampacity 15 A 15 A 15 A 15 A 15 A 15 A 15 A 25 A
Contactor (2)
T02AN13 T02AN13 T02AN13 T02AN13 T02AN13 T02BN13 T02BN13 T02CN13
NEMA size 00 00 00 00 00 0 0 1
SCCR with circuit
breaker shown
85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA
Thermal overload class 20
LRD06L LRD07L LRD07L LRD08L LRD08L LRD10L LRD12L LRD16L
Overload range 1–1.6 A 1.6–2.5 A 1.6–2.5 A 2.5–4 A 2.5–4 A 4–6 A 5.5–8 A 9–13 A
SCCR with circuit
breaker shown
65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA
Electronic overload
LR9D02 LR9D02 LR9D08 LR9D08 LR9D08 LR9D08 LR9D32 LR9D32
Overload range 0.4–2 A 0.4–2 A 1.6–8 A 1.6–8 A 1.6–8 A 1.6–8 A 6.4–32 A 6.4–32 A
SCCR with circuit
breaker shown
5 kA 5 kA 10 kA 10 kA 10 kA 10 kA 65 kA 65 kA
Notes: (1) For alternate interrupting ratings at 480Y/277 V, replace the ‘‘J’’ in the part number with ‘‘D’’ for 18 kA, or ‘‘G’’ for 35 kA.
(2) Complete the contactor part number by adding the coil voltage sufx from TABLE C. For example, T02CN13G7 includes a 120 VAC coil.
Fuse holder + denite purpose (DP) contactor
Motor HP 230 V 1-phase 1/6 1/4 1/3 1/2 3/4 1 1-1/2 2
Full load current
(NEC Table 430.248)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A
Fuse holder 2-pole
9080FB2611J 9080FB2611J 9080FB2611J 9080FB2611J 9080FB2611J 9080FB2611J 9080FB2611J 9080FB2611J
Fuse class/ampacity J 4 A J 5 A J 6 A J 8 A J 12 A J 15 A J 17.5 A J 25 A
SCCR 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA
Contactor 2-pole (1)
8910DP12 8910DP12 8910DP12 8910DP12 8910DP12 8910DP12 8910DP12 8910DP12
Full load amp rating
20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
Resistive load
amp rating
30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
SCCR with fuse
shown
100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Motor HP 460 V 3-phase 1/2 3/4 1 1-1/2 2 3 5 7-1/2
Full load current
(NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A
Fuse holder 3-pole
9080FB3611J 9080FB3611J 9080FB3611J 9080FB3611J 9080FB3611J 9080FB3611J 9080FB3611J 9080FB3611J
Fuse class/ampacity J 2 A J 3 A J 3.5 A J 5 A J 6 A J 8 A J 12 A J 20 A
SCCR 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA
Contactor 3-pole (1)
8910DPA13 8910DPA13 8910DPA13 8910DPA13 8910DPA13 8910DPA13 8910DPA13 8910DPA13
Full load amp rating
20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A
Resistive load
amp rating
30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
SCCR with fuse
shown
100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Notes: (1) Complete the contactor part number by adding the coil voltage sufx from TABLE D (see page 17). For example, 8910DPA33V02 includes a 120 VAC coil.
Circuit
breakers
Motor
circuit
protectors
Fusible
discon-
nects
Non-fused
discon-
nects
Fuse
holders
Manual
motor
protectors
Contactors
Overload
relays
Motor
starters
Combination
motor
controllers
Range name
PPB, Multi 9
TeSys BV4 TeSys GS
TeSys VLS,
MD
TeSys DF
TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Product reference prefix B, M9 BV4 GS VLS, MD DF GV LC LR LZ LU
Motor starter structure - 4 functions:
Disconnect
— — — —
Short-circuit protection
(1)
— (2) — — —
(2)
Motor controller
— — — — — — —
Overload protection
— — — — — —
Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller.