Product Overview

Table Of Contents
19
Consult the Schneider Electric Digest for more product selection options and information.
Disconnect + fuses + contactor + overload relay
Motor HP 460 V 1/2 3/4 1 1-1/2 2 3 5 7-1/2 10
Full load current
(NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A
Fused disconnect (UL 98)
GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DU3
Fuse class/ampacity CC 3 A CC 4.5 A CC 6 A CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A J 25 A
SCCR 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Non-fused disconnect
(UL 98)
VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2
VLS3P063R2
Ampacity 60 A 60 A 60 A 60 A 60 A 60 A 60 A 60 A 60 A
SCCR (max fuse/class)
50 kA
(60 A J)
50kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
50 kA
(60 A J)
Fuse holder
DFCC3 DFCC3 DFCC3 DFCC3 DFCC3 DFCC3 DFCC3 DFCC3
9080FB3611J
Fuse class/ampacity CC 3 A CC 4.5 A CC 6 A CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A J 25 A
SCCR 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA 200 kA
Contactor (2)
LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D18
SCCR with fuse shown 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Thermal overload class 10
LRD06 LRD07 LRD07 LRD08 LRD08 LRD10 LRD12 LRD16 LRD21
Overload range 1–1.6 A 1.6–2.5 A 1.6–2.5 A 2.5–4 A 2.5–4 A 4–6 A 5.5–8 A 9–13 A 12–18 A
SCCR with fuse shown 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Electronic overload
LR9D02 LR9D02 LR9D08 LR9D08 LR9D08 LR9D08 LR9D32 LR9D32 LR9D32
Overload range 0.4–2 A 0.4–2 A 1.6–8 A 1.6–8 A 1.6–8 A 1.6–8 A 6.4–32 A 6.4–32 A 6.4–32 A
SCCR with fuse shown 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
Notes: (2) Complete the contactor part number by adding the coil voltage sufx from TABLE A. For example LC1D09G7 includes a 120 VAC coil.
TeSys™ motor control and protection solutions
24 V 24 V 120 V 100–250 V
LC1 Contactor
AC DC AC AC/DC
D09–D32
B7 BL G7 KUE
D40A–D65A
B7 BBE G7 KUE
D80–D150
B7 BD G7
F115–F330
BD G7
TABLE A:
Voltage coil codes for TeSys LC1 Contactors
Circuit
breakers
Motor
circuit
protectors
Fusible
discon-
nects
Non-fused
discon-
nects
Fuse
holders
Manual
motor
protectors
Contactors
Overload
relays
Motor
starters
Combination
motor
controllers
Range name
PPB, Multi 9
TeSys BV4 TeSys GS
TeSys VLS,
MD
TeSys DF
TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Product reference prefix B, M9 BV4 GS VLS, MD DF GV LC LR LZ LU
Motor starter structure - 4 functions:
Disconnect
Short-circuit protection
(1)
(2)
(2)
Motor controller
Overload protection