Consult the Schneider Electric Digest for more product selection options and information.
TeSys™ motor control and protection solutions
Circuit breaker + contactor + overload relay
``
Motor HP 460 V 1/2 3/4 1 1-1/2 2 3 5 7-1/2 10
Full load current
(NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A
Circuit breaker (1)
BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36015 BJL36025 BJL36030
Interrupting rating 480 V 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA
Ampacity 15 A 15 A 15 A 15 A 15 A 15 A 15 A 25 A 30 A
Contactor (2)
LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D18
SCCR with breaker shown
85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA
Thermal overload class 10
LRD06 LRD07 LRD07 LRD08 LRD08 LRD10 LRD12 LRD16 LRD21
Overload range 1–1.6 A 1.6–2.5 A 1.6–2.5 A 2.5–4 A 2.5–4 A 4–6 A 5.5–8 A 9–13 A 12–18 A
SCCR with breaker shown
65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA
Electronic overload
LR9D02 LR9D02 LR9D08 LR9D08 LR9D08 LR9D08 LR9D32 LR9D32 LR9D32
Overload range 0.4–2 A 0.4–2 A 1.6–8 A 1.6–8 A 1.6–8 A 1.6–8 A 6.4–32 A 6.4–32 A 6.4–32 A
SCCR with breaker shown
5 kA 5 kA 10 kA 10 kA 10 kA 10 kA 65 kA 65 kA 65 kA
Notes: (1) For alternate interrupting ratings at 480Y/277V, replace the ‘‘J’’ in the part number with ‘‘D’’ for 18 kA, or ‘‘G’’ for 35 kA. (2) Complete
the contactor part number by adding the coil voltage sufx from TABLE A. For example, LC1D09G7 includes a 120 VAC coil.
24 V 24 V 120 V 100–250 V
LC1 Contactor
AC DC AC AC/DC
D09–D32
B7 BL G7 KUE
D40A–D65A
B7 BBE G7 KUE
D80–D150
B7 BD G7
F115–F330
BD G7
TABLE A:
Voltage coil codes for TeSys LC1 Contactors
Circuit
breakers
Motor
circuit
protectors
Fusible
discon-
nects
Non-fused
discon-
nects
Fuse
holders
Manual
motor
protectors
Contactors
Overload
relays
Motor
starters
Combination
motor
controllers
Range name PPB, Multi 9 TeSys BV4 TeSys GS
TeSys VLS,
MD
TeSys DF TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Product reference prefix B, M9 BV4 GS VLS, MD DF GV LC LR LZ LU
Motor starter structure - 4 functions:
w
Disconnect
— — — —
Short-circuit protection
(1)
— (2) — — —
(2)
Motor controller
— — — — — — —
Overload protection
— — — — — —
Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller.