Product Overview

Table Of Contents
15
Consult the Schneider Electric Digest for more product selection options and information.
Type E combination motor controller
Motor HP 460 V 1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20
Full load current
(NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A 21 A 27 A
Base (1)
LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB32 LUB32 LUB32 LUB32
Trip unit (2)
LUCA1X LUCA05 LUCA05 LUCA05 LUCA12 LUCA12 LUCA12 LUCA18 LUCA32 LUCA32 LUCA32
Overload range 0.3–1.4 A 1.25–5 A 1.25–5 A 1.25–5 A 3–12 A 3–12 A 3–12 A 4.5–18 A 8–32 A 8–32 A 8–32 A
SCCR 480 Y/277 V 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA
Notes: (1) Type E combination requires use of LU9SP0 line spacer or GV1G09 line spacer. Permissible to use GV2G busbars with GV1G09 to reduce wiring
installation efforts. (2) Complete the contactor part number by adding the coil voltage sufx from TABLE B. For example, LUCA12FU includes a 120 VAC coil.
15
24 V 24 V 120 V 100–250 V
LC1 Contactor
AC DC AC AC/DC
D09–D32
B7 BL G7 KUE
D40A–D65A
B7 BBE G7 KUE
D80–D150
B7 BD G7
F115–F330
BD G7
TABLE A:
Voltage coil codes for TeSys LC1 Contactors
24 V 24 V 120–240 V
AC DC AC/DC
LUC Trip units
B BL FU
TABLE B:
Voltage coil codes for TeSys U Starters
Type F combination motor controller
Motor HP
460 V
1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40
Full load
current
(NEC Table
430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A 21 A 27 A 34 A 40 A 52 A
SCCR
480 Y/277 V
100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
50 kA
(2)
50 kA
(2)
50 kA
(2)
65 kA 65 kA 65 kA 65 kA
Manual motor
protector (1)
GV2P06 GV2P07 GV2P07 GV2P08 GV2P08 GV2P10 GV2P14 GV2P16 GV2P20 GV2P21 GV3P32 GV3P40 GV3P50 GV3P65
Overload
range
1–1.6
A
1.6–2.5
A
1.6–2.5
A
2.5–4
A
2.5–4
A
4–6.3
A
6–10
A
9–14
A
13–18
A
17–23
A
23–32
A
30–40
A
37–50
A
48–65
A
Contactor (3)
LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D18 LC1D25 LC1D25
LC1D40A LC1D40A LC1D50A LC1D65A
Notes: (1) Type F combination requires use of GV1G09 line spacer for GV2 or GV3G66 line spacer for GV3. Permissible to use GV2G busbars with GV1G09
for the GV2 to reduce wiring installation efforts. (2) Type F combination SCCR is 42 kA 480Y / 277V when using GVG2 busbars with GV1G09 on GV2P16 to
GV2P21. (3) Complete the contactor part number by adding the coil voltage sufx from TABLE A. For example, LC1D09G7 includes a 120 VAC coil.
TeSys™ motor control and protection solutions
Circuit
breakers
Motor
circuit
protectors
Fusible
disconnects
Non-fused
disconnects
Fuse
holders
Manual
motor
protectors
Contactors
Overload
relays
Motor
starters
Combination
motor
controllers
Range name
PPB, Multi 9
TeSys BV4 TeSys GS
TeSys VLS,
MD
TeSys DF
TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Product reference prefix B, M9 BV4 GS VLS, MD DF GV LC LR LZ LU
Motor starter structure - 4 functions:
Disconnect
Short-circuit protection
(1)
(2)
(2)
Motor controller
Overload protection
Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller.