Brochure

15-16
© 2019 Schneider Electric
All Rights Reserved
Door Closing Mechanisms
Types M5, M6, M1, and M8
schneider-electric.us
Class 9423 / Refer to Catalog 9420CT9701
15
OPERATING MECHANISMS AND
DISCONNECT SWITCHES
Enclosure Construction and General Location Information For
Types M5 and M6
Drilling and location information below is complete for a single door enclosure with door
hinged on left side, incorporating a Type M6, M5, and Class 9422 handle mechanism.
Transpose all horizontal dimensions for doors hinged on right side.
Dimension A
Single door enclosures: A minimum = 1 in.
Multi-door enclosures without overhead interlocking system:
A minimum = 1 in.
Multi-door enclosures with overhead interlocking system:
A minimum = 4–1/2 in.
NOTE: Overhead interlocking system consists of the required number of Class 9423
Type M2 and M7 kits for interlocking the auxiliary doors with the master door. See
page 15-14.
Table 15.39: Dimension B (Minimum)
Type
Disconnect Device
If A = 1
Minimum B =
If A = 4–1/2
Minimum B =
C
TCF, TCN, TDF, TDN, TD
60 A Disconnect Switch 3-/16 2-1/2 3-3/16
TE, TEF, TEN
100 A Disconnect Switch 5-1/4 2-1/2 3-3/16
TF 200 A Disconnect Switch 11-5/8 8-1/8 3-3/16
TG 400 A Disconnect Switch 15-1/16 11-9/16 6-3/4
RN1
FAL, FHL, Circuit Breaker
4-27/32 2-1/2 3-3/16
RP1
KAL, KHL Circuit Breaker
11-5/32 7-21/32 3-3/16
RR2 ILL Circuit Breaker 17-31/32 14-15/32 3-3/16
RT1
MAL, MHL, MEL, MXL Circuit
Breaker
18-5/8 15-1/8 3-3/16