Troubleshooting Guide
9013DB0701  Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches
12/2007 Troubleshooting
© 2007 Schneider Electric All Rights Reserved
5
Pump cycles 
each time water 
is used
Tank waterlogged 
For pre-charged tanks, check the bladder or air valve for leaks and 
check tank pressure. If it is below cut-in pressure setting, complete 
Steps 1–5 of “Providing Routine Maintenance” on page 1. 
Drain some air from the compressed air valve stem. If water comes out, 
the bladder is leaking. Completely drain the bladder and recharge with 
air as required. Complete the remaining steps under “Providing Routine 
Maintenance” on page 1.
1. Replace or repair the pressure tank.
2. For conventional tanks, check air 
volume control for proper operation. 
Drain and recharge tank. Clean or 
replace any faulty parts.
Pressure switch 
chattering 
(contact chatter 
or bounce)
Incorrect air pressure in the 
bladder 
Adjust the air pressure in the bladder to manufacturer's specification. 
See the procedures for waterlogged tank.
For conventional tanks, check the air 
volume control for proper operation. 
Drain and recharge tank. Clean or 
replace any faulty parts.
Excessive vibration
The pressure switch may be mounted on rigid pipe and secured by 
brackets to the structure. If the pump is also tightly secured, vibration 
may be amplified. 
Mount the pressure switch to a less rigid 
pipe, and shock mount any brackets.
Isolate the switch from other sources of vibration by shock mounting.
Pump shuts off 
immediately after 
startup
High pressure pump or a 
new pump
Add a surge reducer. Order 1530S6G1 for a bag of 50.
Long pump run, 
or pump will not 
shut off
Too many water outlets
Limit the number of devices running at any one time. —
Increase the size of the pump and/or storage tank Replace the components as desired
Worn pump parts —
Check the pump for worn impellers, 
casing, or other close fitting parts.
Water leaks
Check for leaks in service lines. Repair the leaks as required
Plugged discharge pipes
Check for plugged discharge pipes 
resulting in reduced flow. Replace the 
damaged pipes or repair the leaks.
Switch contacts 
burn up
Pump electrical rating is 
too high
—
Ensure that the electrical rating of the 
switch corresponds to the pump’s 
electrical rating.
Add a contactor. 
The switch may be replaced by one with 
heavy duty contacts.
Switch will not 
trip (cut-in/cut-
out) at desired 
pressure
Incorrect pressure settings
Adjust to correct pressure settings. See procedures for waterlogged 
tank on page 4.
—
Defective pressure gauge Test the pressure gauge. Replace the pressure gauge.
Damaged diaphragm 
actuator
— Replace the diaphragm.
Cannot adjust 
switch to desired 
pressure
Settings outside the 
pressure range limits of the 
switch 
—
Replace the switch with one that has 
the correct range and differential
Table 2: Troubleshooting Tips (continued) 
Condition Possible Causes Description/Corrective Action
Corrective Procedure for 
Qualified Service Personnel








